Residual current monitoring in grounded power supplies (TT and TN systems) – VARIMETER RCM
Early detection of insulation faults, as well as preventive maintenance and servicing outside of operating hours, can prevent unexpected shutdowns of machines and systems, thus avoiding unwanted interruptions in operation, property damage and high costs. Residual current monitors of the VARIMETER RCM (Residual Current Monitor) series are available as pure AC currents and pulsating DC currents DC (type A according to IEC/TR 60755) as well as all-current sensitive residual current monitors (type B) AC currents, pulsating and smooth DC residual currents DC.
Residual current monitor, Type A IL 5882

Product Overview
Advantages
- Preventive fire and system protection
- Increasing the availability of plants by early fault detection
- With external residual current transformer
- Protection against manipulation by sealable transparent cover over setting switches
Features
- According to IEC/EN 62020
- For AC and pulsating DC currants Type A to IEC/TR 60755
- 9 tripping values from 10 mA to 10 A or from 10 mA … 30 A
- Frequency range 20 … 2000 Hz
- Selection of manual or automatic reset
- With prewarning
- With test and reset button
- Broken wire detection
- Short reaction time
- With adjustable delay tv
- De-energized on trip
- LED indication for auxiliary supply and state of contact
- 2 x 1 changeover contact
- Devices available in 3 enclosure versions:
IL 5882: 63 mm deep with terminals near to the bottom to be mounted in consumer units or industrial distribution systems according to DIN 43880
– Width 35 mm
– For connection of external residual current transformer, e. g. ND 5016, ND 5019 or split current transformer ND 5014
SL 5882: 100 mm deep with terminals near to the top to be mounted in cabinets with mounting plate and cable ducts
– Width 35 mm
– For connection of external residual current transformer, e. g. ND 5016, ND 5019 or split current transformer ND 5014
Datasheet Download
Residual current monitor, Type A SL 5882

Product Overview
Advantages
- Preventive fire and system protection
- Increasing the availability of plants by early fault detection
- With external residual current transformer
- Protection against manipulation by sealable transparent cover over setting switches
Features
- According to IEC/EN 62020
- For AC and pulsating DC currants Type A to IEC/TR 60755
- 9 tripping values from 10 mA to 10 A or from 10 mA … 30 A
- Frequency range 20 … 2000 Hz
- Selection of manual or automatic reset
- With prewarning
- With test and reset button
- Broken wire detection
- Short reaction time
- With adjustable delay tv
- De-energized on trip
- LED indication for auxiliary supply and state of contact
- 2 x 1 changeover contact
- Devices available in 3 enclosure versions:
IL 5882: 63 mm deep with terminals near to the bottom to be mounted in consumer units or industrial distribution systems according to DIN 43880
– Width 35 mm
– For connection of external residual current transformer, e. g. ND 5016, ND 5019 or split current transformer ND 5014
SL 5882: 100 mm deep with terminals near to the top to be mounted in cabinets with mounting plate and cable ducts
– Width 35 mm
– For connection of external residual current transformer, e. g. ND 5016, ND 5019 or split current transformer ND 5014
Datasheet Download
Residual current monitor, Type B RN 5883

Product Overview
Advantages
- Preventive fire and system protection
- Increasing the availability of plants by early fault detection
- Universal usage at AC/DC mains
- Protection against manipulation by sealable transparent cover over setting switches
Features
- According to IEC/EN 62020, VDE 0663
- For AC and DC systems Type B
- To detect earth faults in grounded voltage systems
- 4 setting ranges from 10 mA to 3 A
- Manual reset, with alarm and pre-warning
- With adjustable switching delay
- Energized or de-energized on trip
- LED indicator for operation, pre-alarm and alarm
- With test function
- LED-chain indicates fault current
- As option with analogue output
- Broken wire detection
- Width: 52.5 mm
Datasheet Download
Residual current monitor, Type A, with integrated transformer IR 5882

Product Overview
Advantages
- Preventive fire and system protection
- Increasing the availability of plants by early fault detection
- With internal residual current transformer
- Protection against manipulation by sealable transparent cover over setting switches
Features
- According to IEC/EN 62020
- For AC and pulsating DC currants Type A to IEC/TR 60755
- 9 tripping values from 10 mA to 10 A or from 10 mA … 30 A
- Frequency range 20 … 2000 Hz
- Selection of manual or automatic reset
- With prewarning
- With test and reset button
- Short reaction time
- With adjustable delay tv
- De-energized on trip
- LED indication for auxiliary supply and state of contact
- 2 x 1 changeover contact
- 63 mm deep with terminals near to the bottom to be mounted in consumer units or industrial distribution systems according to DIN 43880
– Width 105 mm
– With internal residual current transformer