SCU Master Products include: SCU-0-EC, SCU-1-EC, SCU-2-EC
i

SCU-0-EC
Open programmable and configurable FSoE master module for operation on EtherCAT networks.
- Easy integration of safe drives (Safe Drive Profile)
- Fast-channel task with guaranteed processing time of 4 ms
- Safety control unit suitable up to PL e (EN ISO 13849-1) or SIL3 (IEC 61508)
- optional: SARC functionality (kinematics module), FSoE- / PROFIsafe slave stack
The -S variant of the FSoE master is identical to the standard device.
Variants

SCU-0-EC/NM
Open programmable and configurable FSoE master module for operation on EtherCAT networks
- Easy integration of safe drives (Safe Drive Profile)
- Fast-channel task with guaranteed processing time of 4 ms
- Safety control unit suitable up to PL e (EN ISO 13849-1) or SIL3 (IEC 61508)
- optional SARC functionality (kinematics module), FSoE-/ PROFIsafe-slave stack
- Ethernet-based fieldbus interface, safe / non-safe
- Memory card for safety program
- Optional: CIP Safety- stack on request
The -S variant of the FSoE master is identical to the standard device.
Characteristic of the module
Characteristic of the module
- Connection up to 32 FSoE slave units
- Safe logic processing of input, output, status and activation signals
- Simple and transparent programming and parameterization in EtherCAT environment via SafePLC2
- Fast response time with integrated Fast channel task with guaranteed processing time of 4 ms
- Central and decentralized drive monitoring possible
- Complete set of drive monitoring for single axes and calculated axes (based on kinematics function)
- Temporary deteerministic data communication and processing for safe position an speed functions via distributed sensor / multiple axes
- Profiles specifically adaptable to inverter types / manufacturers for process data exchange and central parameterization
- safe cross communication (SMMC: Safe Master- Master Communication) for data exchange between FSoE master via EAP
- Storage of the safe parameters in the SCU master
- Coded status display via front 7-segment display and status LEDs
- Multifunction button (Quit, Start, Reset)
- Optional: integrated communication interface (/NM) :
- Safe kinematics module for up to 6/12 axes with spatial speed and position monitoring
- Additional fieldbus interface and FSoE- / PROFIsafe slave-stack for safe connection to higher control levels
- The mechanical structure of SCU-0-EC (/x*) is dependend on the respective form of the base module
|

SCU-1-EC
Open programmable and configurable FSoE Mastermodule for operation on EtherCAT networks
- 14 safe digital inputs
- Up to 5 safe cutt-off channels
- 2 Relay outputs
- Fast channel task with guaranteed processing time of 4 ms
- Easy integration of safe drives (Safe Drive Profile)
- Safety control suitable up to PL e (EN ISO 13849-1) or SIL3 (IEC 61508)
- Optional: SARC functionality (kinematics module), FSoE / PROFIsafe slave stack
The -S variant of FSoE master is identical to the standard device.
Variants

SCU-1-EC/NM
Open programmable and configurable FSoE Masteer module for operation on EtherCAT networks
- 14 safe digital inputs
- Up to 5 safe cut-off channels
- 2 Relay outputs
- Fast channel task with guaranteed processing time of 4 ms
- Easy integration of safe drives (Safe Drive Profile)
- Safety control suitable up to PL e (EN ISO 13849-1) or SIL3 (IEC 61508)
- Optional: SARC functionality (kinematics module), FSoE-/ PROFIsafe slave stack
- Ethernet-based fieldbus interface, safe / non-safe
- Memory card for safety program
- Optional: CIP Safety- Stack on request
The -S variant of FSoE master is identical to the standard device.
Characteristic of the module
Characteristic of the module
- Connection of max. 32 FSoE slave modules
- Safe logic processing of input, output, status and activation signals
- Simple and transparent programming and parameterization in the EtherCAT environment with SafePLC2
- Fast response time with integrated Fast channel task with guaranteed processing time of 4 ms
- Central or decentralized drive monitoring possible
- Complete set of Drive monitoring of single axes and calculated axes (based on kinematics function)
- Temporary deterministic data exchange and central parametrization that can be adapt to converter/manufacture
- Profiles specifically adaptable to inverter types / manufacturers for process data exchange and central parameterization
- Safe cross communication (SMMC: Safe Master-Master Communication) for data exchange between FSoE Master via EAP
- Storage of safe parameters in SCU master
- Coded status display via front-side 7 segment display and status LEDs
- Multifunction button (Quit, Start, Reset) can be operated from the front side
- Optional: integrated communication interface (/NM):
- safe kinematics module for up to 6/12 axes with spatial speed and position monitoring
- additional fielbus interface and FSoE slave- / PROFIsafe stack for safe connection to higher control levels
- The mechanical structure of SCU-1-EC (/x*) is depended on the respective form of the base module
* Optional: integrated communication interface (/NM)
|

SCU-2-EC
Open programmable and configurable FSoE master unit for operation on EtherCAT networks
- 14 safe digital inputs
- Up to 20 safe digital I/O’s
- 2 Relay outputs
- Fast- channel task with guaranteed processing time of 4 ms
- Simple integration of safe drives (Safe Drive Profile)
- Safety control suitable up to PL e (EN ISO 13849-1) or SIL3 (IEC 61508)
- Optional: SARC functionality (kinematics module), FSoE- / PROFIsafe slave stack
The -S variant of the FSoE master is identical to the standard device.
Variants

SCU-2-EC/NM
Open programmable and configurable FSoE Masteer module for operation on EtherCAT networks
- 14 safe digital inputs
- Up to 5 safe cut-off channels
- 2 Relay outputs
- Fast channel task with guaranteed processing time of 4 ms
- Easy integration of safe drives (Safe Drive Profile)
- Safety control suitable up to PL e (EN ISO 13849-1) or SIL3 (IEC 61508)
- Optional: SARC functionality (kinematics module), FSoE-/ PROFIsafe slave stack
- Ethernet-based fieldbus interface, safe / non-safe
- Memory card for safety program
- Optional: CIP Safety- Stack on request
The -S variant of FSoE master is identical to the standard device.
Characteristic of the module
- Connection of up to 32 FSoE slave modules
- Safe logic processing of input, output, status and activation signals
- Easy and transparent programming and parameterization in the EtherCAT environment via SafePLC2
- Fast response time with integrated Fast channel task with guaranteed processing time of 4 ms
- Central or decentralized drive monitoring possible
- Complet set of drive monitoring for single axis and calculated axes (based on kinematics function)
- Temporary deterministic data communication and processing for safe position and speed functions via distributed sensor / multiples axes
- Specific profiles for process data exchange and central parameterization that can be adapted to converter / manufacture
- Safe cross communication (SMMC: Safe Master-Master Communication) for data exchange between FSoE masters via EAP
- STorage of safe parameters in SCU master unit
- Coded status display via front-side 7 segment display and status LEDs
- Multifunction button (Quit, Start, Reset), front-side
- Optional: integrated communication interface (/NM):
- safe kinematics module for up to 6/12 axes with spatial speed and position monitoring
- additional fieldbus interface and PROFIsafe- / FSoE slave stack for safe connection to higher control levels
- Memory card slot for safety program
- The mechanical structure of SCU-2-EC (/x*) is depended on the respective forms of the base module
* Optional: integrated communication interface (/NM