Measuring relays for power generation systems

You are here:

VARIMETER NA – The grid under control

With its voltage and frequency monitors of the VARIMETA NA series, DOLD offers a safe and standards-conform solution for optimal grid monitoring during energy input into the public grid. The devices are used for voltage and frequency monitoring for decentralised in-house power generation systems.

Voltage and frequency monitor RP 9800

Advantages

  • Easy adjustment via rotational switch
  • Precise adjustment and indication of setting values
  • Protection against manipulation by sealable transparent cover over setting switches

Features

  • According to DIN EN 60255-1, DIN EN 60947-1
  • Voltage and frequency monitoring for generator sets > 30 kVA on public grid, according to VDEW directive
  • RP 9800: 3-phase voltage measurement to neutral
  • Disconnection on rise and drop of voltage
  • Disconnection on rise and drop of frequency
  • Disconnection when 10 minute mean value differs to nominal voltage (overvoltage)
  • Frequency and voltage are indicated by separate output relays
  • Permits connection or re-connection after adjustable time delay tw
  • High measuring accuracy
  • Width 70 mm
 

Voltage and frequency monitor RP 9811

 

Advantages

  • Mains and system protection for your generator set
  • Can be used in several countries
    – DIN VDE 0126-1-1:2013-08 (generator sets on public grid)
    – VDE-AR-N 4105:2011-08 (generator sets on public grid)
    – BDEW-directive:2008-06 (generator sets on medium voltage grid)
    – CEI 0-21:2012-06 (generator sets in Italy)
    – ÖVE/ÖNORM E8001-4-712:2009 (generator sets in Austria)
    – G59/3 (generator sets in UK)
  • Easy adjustment via rotational switch and menu display
  • Indication, diagnostics and fault presentation via display and LEDs
  • Password protected
  • Protection against manipulation by sealable transparent cover over setting switches
  • CRC-value for parameter testing
  • Adjustment of the voltage for nominal voltage will change the limit values accordingly
  • Mains synchronization on generator operation

Features

  • According to DIN EN 60255-1
  • Can be used according to EEG 2012 and SysStabV
  • Voltage and frequency monitoring for generator sets
  • Fail-safe 2-channel structure
  • Monitoring of the section switches by measuring the response time
  • System test via test button
  • Enabling inputs allow integration into various ripple control and plant concepts
  • Isolated grid detection
  • Manual reset
  • Memorising of disconnection time
  • Connection or re-connection after adjustable delay time tOn
  • Factory setting according to:
    VDE-AR-N 4105:2011-08, DIN VDE 0126-1-1:2013-08,
    BDEW-directive:2008-06, CEI 0-21:2012-06,
    ÖVE/ÖNORM E8001-4-712:2009, G59/3 LV
  • Random controlled disconnection in the range of 50.2 Hz and 51.5 Hz for non-regulated power generation systems
  • Random operated connection time (ton) setting range 60…600 s
  • Additional fault signalling relay output
  • High measuring accuracy
  • Installion type enclosure 4TE (width x height x depth: 70 x 90 x 71 mm)

Voltage and frequency monitor according to VDE-AR-N 4105:2011-08 RP 9810

Advantages

  • Easy adjustment via rotational switch
  • Precise adjustment and indication of setting values
  • Indication, diagnostics and fault presentation via display
  • Protection against manipulation by sealable transparent cover over setting switches
  • Mains and system protection for your generator set

Features

  • According to VDE-AR-N 4105:2011-08
  • Following DIN VDE 0126-1-1:2013-08
  • According to DIN EN 60255-1
  • Can be used according to EEG 2012 and SysStabV
  • Voltage and frequency monitoring for generator sets >30 kVA on public grid, as option also for ≤ 30kVA
  • Fail-safe because of 2-channel structure
  • Certificate of conformity (test certificate) of the BG ETEM
  • Monitoring of the section switches with measuring of response time
  • System test via test button
  • Isolated grid detection
  • Manual reset
  • With additional enabling input, e.g. for ripple control receiver
  • Connection or re-connection after adjustable delay time tw
  • Factory setting according to VDE-AR-N 4105:2011-08
  • Random controlled disconnection in the range of 50.2 Hz and 51.5 Hz for non-regulated power generation systems
  • Protection against manipulation by sealable transparent cover over setting switches
  • Additional fault signalling relay output
  • High measuring accuracy
  • Installion type enclosure 4TE (width x height x depth: 70 x 90 x 71 mm)

For all your automation project needs:

Get in touch with us today!