Insulation monitoring of unearthed power supplies (IT systems) – VARIMETER IMD

Insulation monitors, also called IMD (Insulation Monitoring Device), monitor the insulation resistance in unearthed AC, AC/DC and DC power supplies (IT systems). This involves measuring the insulation resistance of the IT system to be monitored against earth. These systems are protected by insulation monitoring devices, the use of which is required by law in IT systems by the “Safety of Machinery” standard. Insulation monitoring devices are used to prevent accidents in the event of insulation faults, to prevent failures and generally to protect against fire and accidents.

Insulation monitor MK 5880N

Features

  • According to IEC/EN 61557-8
  • For single and 3-phase AC-systems up to 0 … 500 V and 10 … 1000 Hz
  • Monitors also disconnected voltage systems
  • Adjustable tripping value RAL of 5 … 100 kΩ
  • De-energized on trip
  • Auxiliary voltage, measuring circuit and output contacts are galvanically separated
  • Manual and auto reset
  • With test and reset button
  • Connections for external test and reset buttons possible
  • LED indicators for operation and alarm
  • 2 changeover contacts
  • MK 5880N/200 with additional prewarning
    – Adjustable prewarning value 10 kΩ … 5 MΩ
    – 1 output relay for alarm and 1 for pre-warning
  • MH 5880/500: similar to MK 5880N but with galvanic separated analogue output and 11 step LED chain for the actual insulation value
  • Wire connection: also 2 x 1.5 mm2 stranded ferruled, or 2 x 2.5 mm2 solid DIN 46 228-1/-2/-3/-4
  • As option with pluggable terminal blocks for easy exchange of devices
    – With screw terminals
    – Or with cage clamp terminals
  • MK 5880N: 22.5 mm width
    MH 5880: 45 mm width

Insulation monitor IL 5880

Advantages

  • Preventive fire and system protection
  • For single and 3-phase AC-systems up to 0 … 500 V and 10 … 10000 Hz
  • Monitors also disconnected voltage systems
  • Easy adjustment of response values

Features

  • According to IEC/EN 61557-8
  • Adjustable tripping value RAL of 5 … 100 kΩ or 10 … 500 kΩ
  • De-energized on trip
  • Auxiliary voltage Measuring Circuit and output contacts are galvanically separated
  • Manual and auto reset
  • With test and reset button
  • Connections of external test and reset buttons possible
  • LED indicators for operation and alarm
  • 2 changeover contacts
  • IL/SL 5880/200 with additional prewarning
    – Adjustable prewarning value 10 kΩ … 5 MΩ
    – Output function programmable
  • Variant IL/SL 5880/300 according to DIN VDE 0100-551 for mobile generator sets available
  • 4 models available:
    IL 5880, IP 5880: 61 mm deep with terminals near to the bottom to be mounted in consumer units or industrial distribution systems according to DIN 43880
    SL 5880, SP 5880: 98 mm deep with terminals near to the top to be mounted in cabinets with mounting plate and cable ducts
  • DIN rail or screw mounting
  • 35 mm width

Insulation monitor IL 5881

Advantages

  • Preventive fire and system protection
  • For DC voltage systems up to 12 … 280 V
  • Wide voltage range of measuring input UN DC 12 … 280 V (on request DC 24 … 500 V with separate auxiliary supply, Measuring range 20 … 500 kΩ)
  • Easy adjustment of response value
  • Selective ground fault indication for L+ and L- allows fast fault finding

Features

  • With reference to IEC/EN 61557-8 (see also section “Notes”)
  • Adjustable tripping value RAL of 5 … 200 kΩ or 10 … 500 kΩ
  • Selective ground fault indication for L+ and L- allows fast fault finding
  • Without auxiliary supply
  • De-energized on trip
  • 2 changeover contacts
  • Automatic or manual reset, programmable
  • With test and reset buttons
  • Connection for external test and reset button possible
  • Galvanic separated AC or DC auxiliary supply available as option
  • Adjustable time delay as option
  • 2 models available:
    IL 5881: 61 mm deep with terminals near to the bottom to be mounted in consumer units or industrial distribution systems according to DIN 43880
    SL 5881: 98 mm deep with terminals near to the top to be mounted in cabinets with mounting plate and cable ducts
  • DIN rail or screw mounting
  • 35 mm width

Insulation monitor RL 5881

Advantages

  • Preventive fire and system protection
  • Detection of symmetric and asymmetric insulation faults
  • For non-earthed DC voltage networks up to 300 V
  • Suitable for large leakage capacitances up to 30 μF
  • Monitoring also with voltage-free mains
  • No additional coupling device required

Features

  • Insulation monitoring according to IEC/EN 61557-8
  • Adjustable response threshold, Setting range: 1 kΩ … 300 kΩ
  • 1 changeover contacts for insulation failure alarm
  • De-energized on trip
  • Energized on trip on request
  • With multicolour status LED to indicate the state of operation
  • Automatic and manual device self-test
  • Manual reset or hysteresis function selectable (programmable via control input)
  • Protection against manipulation by sealable transparent cover
  • Control input for external test and reset-button
  • 2 wide voltage input for auxiliary voltage
  • RL 5881/100 without auxiliary voltage
  • Width 35 mm

Insulation monitor RL 5889

Advantages

  • Preventive fire and system protection
  • Detection of symmetric and asymmetric insulation faults
  • Universal application in non-earthed AC, DC, AC/DC networks up to max. 300 V
  • Suitable for large leakage capacitances up to 30 μF
  • Monitoring also with voltage-free mains

Features

  • Insulation monitoring according to IEC/EN 61557-8
  • Adjustable response threshold, Setting range: 1 kΩ … 300 kΩ
  • 1 changeover contacts for insulation failure alarm
  • Energized or de-energized on trip can be selected for indicator relay
  • With multicolour status LED to indicate the state of operation
  • Automatic and manual device self-test
  • Manual reset or hysteresis function selectable (programmable via control input)
  • Protection against manipulation by sealable transparent cover
  • Control input for external test- / reset-button
  • 2 wide voltage input for auxiliary voltage
  • Width 35 mm

Insulation monitor SL 5880

Advantages

  • Preventive fire and system protection
  • For single and 3-phase AC-systems up to 0 … 500 V and 10 … 10000 Hz
  • Monitors also disconnected voltage systems
  • Easy adjustment of response values

Features

  • According to IEC/EN 61557-8
  • Adjustable tripping value RAL of 5 … 100 kΩ or 10 … 500 kΩ
  • De-energized on trip
  • Auxiliary voltage Measuring Circuit and output contacts are galvanically separated
  • Manual and auto reset
  • With test and reset button
  • Connections of external test and reset buttons possible
  • LED indicators for operation and alarm
  • 2 changeover contacts
  • IL/SL 5880/200 with additional prewarning
    – Adjustable prewarning value 10 kΩ … 5 MΩ
    – Output function programmable
  • Variant IL/SL 5880/300 according to DIN VDE 0100-551 for mobile generator sets available
  • 4 models available:
    IL 5880, IP 5880: 61 mm deep with terminals near to the bottom to be mounted in consumer units or industrial distribution systems according to DIN 43880
    SL 5880, SP 5880: 98 mm deep with terminals near to the top to be mounted in cabinets with mounting plate and cable ducts
  • DIN rail or screw mounting
  • 35 mm width
 

Insulation monitor SL 5881

Advantages

  • Preventive fire and system protection
  • For DC voltage systems up to 12 … 280 V
  • Wide voltage range of measuring input UN DC 12 … 280 V (on request DC 24 … 500 V with separate auxiliary supply, Measuring range 20 … 500 kΩ)
  • Easy adjustment of response value
  • Selective ground fault indication for L+ and L- allows fast fault finding

Features

  • With reference to IEC/EN 61557-8 (see also section “Notes”)
  • Adjustable tripping value RAL of 5 … 200 kΩ or 10 … 500 kΩ
  • Selective ground fault indication for L+ and L- allows fast fault finding
  • Without auxiliary supply
  • De-energized on trip
  • 2 changeover contacts
  • Automatic or manual reset, programmable
  • With test and reset buttons
  • Connection for external test and reset button possible
  • Galvanic separated AC or DC auxiliary supply available as option
  • Adjustable time delay as option
  • 2 models available:
    IL 5881: 61 mm deep with terminals near to the bottom to be mounted in consumer units or industrial distribution systems according to DIN 43880
    SL 5881: 98 mm deep with terminals near to the top to be mounted in cabinets with mounting plate and cable ducts
  • DIN rail or screw mounting
  • 35 mm width

Insulation monitor AI 897

Features

  • According to IEC/EN 61557-8
  • For single- and 3-phase AC-voltage systems
  • Adjustable response value RAN from 10 … 80 kΩ
  • Without auxiliary supply
  • Closed circuit operation
  • Programmable for:
    – Manual reset (bridge LT1-LT2)
    – Automatic reset (without bridge)
  • External reset button on LT1-LT2
  • Test button to check the function of the device
  • External test button can be connected to PT1-PT2
  • 1 changeover contact
  • Width 45 mm

Insulation monitor MH 5880

Features

  • According to IEC/EN 61557-8
  • For single and 3-phase AC-systems up to 0 … 500 V and 10 … 1000 Hz
  • Monitors also disconnected voltage systems
  • Adjustable tripping value RAL of 5 … 100 kΩ
  • De-energized on trip
  • Auxiliary voltage, measuring circuit and output contacts are galvanically separated
  • Manual and auto reset
  • With test and reset button
  • Connections for external test and reset buttons possible
  • LED indicators for operation and alarm
  • 2 changeover contacts
  • MK 5880N/200 with additional prewarning
    – Adjustable prewarning value 10 kΩ … 5 MΩ
    – 1 output relay for alarm and 1 for pre-warning
  • MH 5880/500: similar to MK 5880N but with galvanic separated analogue output and 11 step LED chain for the actual insulation value
  • Wire connection: also 2 x 1.5 mm2 stranded ferruled, or 2 x 2.5 mm2 solid DIN 46 228-1/-2/-3/-4
  • As option with pluggable terminal blocks for easy exchange of devices
    – With screw terminals
    – Or with cage clamp terminals
  • MK 5880N: 22.5 mm width
    MH 5880: 45 mm width

Insulation monitor UH 5892

Advantages

  • Preventive fire and system protection
  • Insulation monitoring of DC voltage systems up to 600 V nominal voltage
  • No additional coupling device required
  • Suitable for leakage capacitances up to 20 μF
  • Monitoring also with voltage-free mains
  • 2 wide voltage input ranges for auxiliary voltage

Features

  • Insulation monitoring according to IEC/EN 61557-8
  • Detection of symmetric and asymmetric insulation faults
  • 1 changeover contact for alarm
  • Fixed response value RAN: 50 kΩ, other on request
  • Internal reset and test pushbutton
  • External test and reset pushbutton can be connected
  • LED indicator for auxiliary voltage and alarm
  • LED chain to indicate the current insulation resistance
  • Automatic or manual reset, programmable
  • Analogue output for insulating value
  • External indicating instrument can be connected
  • Closed circuit operation
  • Open circuit operation on request
  • With pluggable terminal blocks for easy exchange of devices
    – with screw terminals
    – or with cage clamp terminals
  • Width 45 mm

Insulation monitor IN 5880/711

Features

  • According to IEC/EN 61 557-8
  • For rooms used for medical purposes
    according to IEC 60364-7-710, DIN VDE 0100-710
  • For three-phase and A.C. power systems with 0 … 500 V
    and 10 … 1000 Hz (IT power systems)
  • Adjustable alarm value for ground fault RAL of 50 … 500 kΩ
  • Measuring circuit with broken wire protection
  • As option, programmable for storing or non-storing of errors
  • With reset and test button
  • Additional external reset and test buttons can be connected
  • LED indicators for operation, insulation fault, and interruption of Measuring circuit
  • 2 changeover contacts
  • With LED chain for indication of the current insulation status
  • IP 5880/711 for connection of the test and display panel UP 5862
  • 52.5 mm width

Insulation monitor RN 5893

Advantages

  • Suitable for DC charging stations for electric vehicles acc. to IEC/EN 61851-23:2014/AC:2016-06
  • Preventive fire and system protection
  • Detection of symmetric and asymmetric insulation faults
  • Quick fault localisation through selective earth fault detection to L+ and L-
  • Universal application in non-earthed AC, DC, AC/DC networks up to AC max. 250 V or DC max. 300 V
  • With connection facility of an external coupling device RP 5898 for voltages up to AC 690 V / DC 1000 V
  • RN 5893: Very fast reaction time ≤ 1 s
    RN 5893/010: Reaction time < 10 s
  • Optimised insulation resistance monitoring also during mains voltage variation
  • Easy adjustment of response values and setting parameter via rotational switch and menu display or via Modbus RTU-interface
  • RN 5893: Suitable for leakage capacitances up to 5 μF
    RN 58930/010: Suitable for leakage capacitances up to 30 μF
  • Monitoring also with voltage-free mains
  • Measuring circuit L(+)/L(-) with broken wire detection (can be switched off)
  • Protective conductor PE1/PE2 with broken wire detection (can’t be switched off)
  • 2 parameterizable changeover contacts (for insulation fault pre-alarm, insulation fault-alarm, insulation fault-alarm on DC+/DC- or device fault) each galvanic separated
  • With galvanic separated Modbus RTU interface

Features

  • Insulation monitoring according to IEC/EN 61557-8
  • 2 separate adjustable response thresholds (using e.g. for pre-alarm and alarm)
  • Setting value pre-alarm: 1 kΩ … 500 kΩ
  • Setting value alarm: 1 kΩ … 500 kΩ
  • Energized or de-energized on trip can be selected for indicator relay
  • Display for indication of measured value, device parameters and device status
  • Manual device self-test (automatic device self-test)
  • Alarm storage selectable
  • Protection against manipulation by sealable transparent cover
  • External control input for combined test- / reset-button with additional Stop of the measuring function
  • 2 wide voltage input for auxiliary voltage
  • Width 52.5 mm

Insulation monitor RN 5893/100

Advantages

  • Suitable for DC charging stations for electric vehicles acc. to IEC/EN 61851-23:2014/AC:2016-06
  • Insulation monitoring according to IEC/EN 61557-8
  • Universal application in non-earthed AC-, DC-, AC/DC networks up to AC max. 250 V resp. DC max. 300 V
  • Connection of an external coupling device RP 5898 for voltages up to AC 690 V / DC 1000 V possible
  • Extended operating temperature range of – 40 … + 70 °C
  • Very fast reaction time ≤ 1 s
  • Optimised insulation resistance monitoring also during mains voltage variation
  • Preventive fire and system protection
  • Detection of symmetric and asymmetric insulation faults
  • Easy adjustment of response values and setting parameter via Modbus
  • Suitable for leakage capacitances up to 5 μF
  • Monitoring also with voltage-free mains
  • Measuring circuit L(+)/L(-) with broken wire detection (can be switched off)
  • Protective conductor PE1/PE2 with broken wire detection (can’t be switched off)
  • With galvanic separated Modbus RTU interface

Features

  • 2 separate adjustable response thresholds (using e.g. for pre-alarm and Alarm)
  • Setting range pre-alarm: 1 kΩ … 500 kΩ
  • Setting range alarm: 1 kΩ … 500 kΩ
  • 2 parameterizable changeover contacts (for insulation fault pre-alarm, insulation fault-alarm, insulation fault-alarm on DC+/DC- or device fault) each galvanic separated
  • Energized or de-energized on trip can be selected for indicator relay
  • With multicolour status LED to indicate the state of operation.
  • Manual device self-test (automatic device self-test can be activated)
  • Alarm storage selectable
  • Protection against manipulation by sealable transparent cover
  • External control input for combined test- / reset-button with additional Stop of the measuring function
  • 2 wide voltage input for auxiliary voltage
  • Width 52.5 mm

Insulation monitor RN 5897

Advantages

  • Acc. to DIN VDE 0100-551 for mobile generator sets
  • Preventive fire and system protection
  • Detection of symmetric and asymmetric insulation faults
  • Quick fault localisation through selective earth fault detection to L+ and L-
  • Universal application in non-earthed AC, DC, AC/DC networks up to 300 V
  • Easy adjustment of response values and setting parameter via rotational switch and menu display
  • Suitable for large leakage capacitances up to 300 μF
  • Optimised reaction time for large leakage capacitances
  • Monitoring also with voltage-free mains
  • Measuring circuit L(+)/L(-) with broken wire detection (can be switched off)
  • Protective conductor PE1/PE2 with broken wire detection (can’t be switched off)
  • No additional coupling device required

Features

  • Insulation monitoring according to IEC/EN 61557-8
  • 2 separate adjustable response thresholds (using e.g. for pre-Alarm and Alarm)
  • Setting range of 1st response value (Pre-Alarm): 20 kΩ … 500 kΩ
  • Setting range of 2nd response value (Alarm): 15 kΩ … 100 kΩ
  • 2 changeover contacts für insulation failures-Pre-Alarm and -Alarm
  • Energized or de-energized on trip can be selected for indicator relay
  • Display for indication of measured value, device parameters and device status
  • Setting the maximum leakage capacitance to shorten the response time
  • Automatic and manual device self-test
  • Alarm storage selectable
  • Protection against manipulation by sealable transparent cover
  • External control input for combined Test-/Reset-button
  • 3 wide voltage input for auxiliary voltage
  • Width 52.5 mm

Insulation monitor RN 5897/010

Advantages

  • Preventive fire and system protection
  • Detection of symmetric and asymmetric insulation faults
  • Quick fault localisation through selective earth fault detection to L+ and L-
  • Universal application in non-earthed AC, DC, AC/DC networks up to AC max. 250 V or DC max. 300 V
  • With connection facility of an external coupling device:
    RL 5898 for voltages up to AC 400 V / DC 500 V
    RP 5898 for voltages up to AC 690 V / DC 1000 V
    RR 5898*) for voltages up to AC 1000 V / DC 1500 V
  • Easy adjustment of response values and setting parameter via rotational switch and menu display
  • Suitable for large leakage capacitances up to 1000 μF
  • Optimised reaction time for large leakage capacitances
  • Monitoring also with voltage-free mains
  • Measuring circuit L(+)/L(-) with broken wire detection (can be switched off)
  • Protective conductor PE1/PE2 with broken wire detection (can’t be switched off)

Features

  • Insulation monitoring according to IEC/EN 61557-8
  • Trigger output for insulation fault locating system
  • 2 separate adjustable response thresholds (using e.g. for pre-Alarm and Alarm)
  • Setting range of 1st response value (Pre-Alarm): 20 kΩ … 2 MΩ
  • Setting range of 2nd response value (Alarm): 1 kΩ … 250 kΩ
  • 2 changeover contacts für insulation failures-Pre-Alarm and -Alarm
  • Energized or de-energized on trip can be selected for indicator relay
  • Display for indication of measured value, device parameters and device status
  • Setting the maximum leakage capacitance to shorten the response time
  • Automatic and manual device self-test
  • Alarm storage selectable
  • Protection against manipulation by sealable transparent cover
  • External control input for combined Test-/Reset-button
  • 3 wide voltage input for auxiliary voltage
  • Width 52.5 mm

Insulation monitor RN 5897/011

Advantages

  • Preventive fire and system protection
  • Detection of symmetric and asymmetric insulation faults
  • Quick fault localisation through selective earth fault detection to L+ and L-
  • Universal application in non-earthed AC, DC, AC/DC networks up to AC max. 250 V or DC max. 300 V
  • With connection facility of an external coupling device:
    RL 5898 for voltages up to AC 400 V / DC 500 V
    RP 5898 for voltages up to AC 690 V / DC 1000 V
    RR 5898*) for voltages up to AC 1000 V / DC 1500 V
  • Easy adjustment of response values and setting parameter via rotational switch and menu display or via Modbus RTU-interface
  • Suitable for large leakage capacitances up to 1000 μF
  • Optimised reaction time for large leakage capacitances
  • Monitoring also with voltage-free mains
  • Measuring circuit L(+)/L(-) with broken wire detection (can be switched off)
  • Protective conductor PE1/PE2 with broken wire detection (can’t be switched off)
  • 2 changeover contacts each for insulation failures-Pre-alarm and -alarm each galvanically isolated
  • With galvanic separated Modbus RTU interface

Features

  • Insulation monitoring according to IEC/EN 61557-8
  • Trigger output for insulation fault locating system
  • 2 separate adjustable response thresholds (using e.g. for pre-Alarm and Alarm)
  • Setting range of 1st response value (Pre-Alarm): 1 kΩ … 2 MΩ
  • Setting range of 2nd response value (Alarm): 1 kΩ … 2 MΩ
  • Energized or de-energized on trip can be selected for indicator relay
  • Display for indication of measured value, device parameters and device status
  • Setting the maximum leakage capacitance to shorten the response time
  • Automatic and manual device self-test
  • Alarm storage selectable
  • Protection against manipulation by sealable transparent cover
  • External control input for combined Test-/Reset-button
  • 2 wide voltage input for auxiliary voltage
  • Width 52.5 mm

Insulation monitor RN 5897/020

Advantages

  • Suitable for DC charging stations for electric vehicles acc. to IEC/EN 61851-23:2014/AC:2016-06
  • Insulation monitoring according to IEC/EN 61557-8
  • With connection facility of an external coupling device RL 5898 for voltages up to AC 400 V / DC 500 V or RP 5898 for voltages up to AC 690 V / DC 1000 V
  • Very fast reaction time ≤ 1 s
  • Optimised insulation resistance monitoring also during mains voltage variation
  • Self-test every full operating hours
  • Preventive fire and system protection
  • Detection of symmetric and asymmetric insulation faults
  • Quick fault localisation through selective earth fault detection to L+ and L-
  • Universal application in non-earthed AC, DC, AC/DC networks up to AC max. 250 V or DC max. 300 V
  • Easy adjustment of response values and setting parameter via rotational switch and menu display
  • Suitable for large leakage capacitances up to 5 μF
  • Monitoring also with voltage-free mains
  • Measuring circuit L(+)/L(-) with broken wire detection (can be switched off)
  • Protective conductor PE1/PE2 with broken wire detection (can’t be switched off)

Features

  • 2 separate adjustable response thresholds (using e.g. for pre-alarm and Alarm)
  • Setting range of 1st response value (Pre-alarm): 20 kΩ … 500 kΩ
  • Setting range of 2nd response value (alarm): 1 kΩ … 100 kΩ
  • 1 changeover contacts each for insulation failures-Pre-alarm and -alarm
  • Energized or de-energized on trip can be selected for indicator relay
  • Display for indication of measured value, device parameters and device status
  • Automatic and manual device self-test
  • Alarm storage selectable
  • Protection against manipulation by sealable transparent cover
  • External control input for combined test- / reset-button with additional Stop of the measuring function
  • 3 wide voltage input for auxiliary voltage
  • Width 52.5 mm

Insulation monitor RN 5897/021

Advantages

  • Suitable for DC charging stations for electric vehicles acc. to IEC/EN 61851-23:2014/AC:2016-06
  • Preventive fire and system protection
  • Detection of symmetric and asymmetric insulation faults
  • Quick fault localisation through selective earth fault detection to L+ and L-
  • Universal application in non-earthed AC, DC, AC/DC networks up to AC max. 250 V or DC max. 300 V
  • With connection facility of an external coupling device RL 5898 for voltages up to AC 400 V / DC 500 V or RP 5898 for voltages up to AC 690 V / DC 1000 V
  • Very fast reaction time ≤ 1 s
  • Optimised insulation resistance monitoring also during mains voltage variation
  • Self-test every full operating hours
  • Easy adjustment of response values and setting parameter via rotational switch and menu display or via Modbus RTU-interface
  • Suitable for large leakage capacitances up to 5 μF
  • Monitoring also with voltage-free mains
  • Measuring circuit L(+)/L(-) with broken wire detection (can be switched off)
  • Protective conductor PE1/PE2 with broken wire detection (can’t be switched off)
  • 2 changeover contacts each for insulation failures-Pre-alarm and alarm each galvanically isolated
  • With galvanic separated Modbus RTU interface

Features

  • Insulation monitoring according to IEC/EN 61557-8
  • 2 separate adjustable response thresholds (using e.g. for pre-alarm and Alarm)
  • Setting range of 1st response value (Pre-alarm): 1 kΩ … 500 kΩ
  • Setting range of 2nd response value (alarm): 1 kΩ … 500 kΩ
  • Energized or de-energized on trip can be selected for indicator relay
  • Display for indication of measured value, device parameters and device status
  • Automatic and manual device self-test
  • Alarm storage selectable
  • Protection against manipulation by sealable transparent cover
  • External control input for combined test- / reset-button with additional Stop of the measuring function
  • 2 wide voltage input for auxiliary voltage
  • Width 52.5 mm

Insulation monitor RN 5897/240

Advantages

  • Insulation monitoring according to IEC/EN 61557-8
  • Suitable for DC charging stations for electric vehicles acc. to IEC/EN 61851-23:2014/AC:2016-06
  • Universal application in non-earthed AC, DC, AC/DC networks up to AC max. 250 V or DC max. 300 V
  • With connection facility of an external coupling device RL 5898 for voltages up to AC 400 V / DC 500 V or RP 5898 for voltages up to AC 690 V / DC 1000 V
  • Extended operating temperature range of – 40 … + 70 °C
  • Very fast reaction time ≤ 1 s
  • Optimised insulation resistance monitoring also during mains voltage variation
  • Self-test every full operating hours
  • Preventive fire and system protection
  • Detection of symmetric and asymmetric insulation faults
  • Universal application in non-earthed AC, DC, AC/DC networks
  • Easy adjustment of response value and setting parameter via rotational switch
  • Suitable for large leakage capacitances up to 5 μF
  • Monitoring also with voltage-free mains
  • Measuring circuit L(+)/L(-) with broken wire detection (can be switched off)
  • Protective conductor PE1/PE2 with broken wire detection (can’t be switched off)

Features

  • Setting range of 2nd response value (alarm): 1 kΩ … 500 kΩ
  • 1 changeover contacts each for insulation failures alarm and device failures
  • Energized or de-energized on trip can be selected for indicator relay
  • With multicolour status LED to indicate the state of operation.
  • Automatic and manual device self-test
  • Alarm storage selectable
  • Protection against manipulation by sealable transparent cover
  • External control input for combined test- / reset-button with additional stop of the measuring function
  • With semiconductor output to indicate the insulation resistance (PWM)
  • 3 wide voltage input for auxiliary voltage
  • Width 52.5 mm

Insulation monitor RN 5897/300

Advantages

  • For mobile generator sets according to DIN VDE 0100-551
  • Preventive fire and system protection
  • Detection of symmetric and asymmetric insulation faults
  • Universal application in non-earthed AC, DC, AC/DC networks up to max. 300 V
  • Easy adjustment of response values and setting parameter via rotational switch
  • Suitable for large leakage capacitances up to 30 μF
  • Monitoring also with voltage-free mains
  • Measuring circuit L(+)/L(-) with broken wire detection (can be switched off)
  • Protective conductor PE1/PE2 with broken wire detection (can’t be switched off)
  • No additional coupling device required

Features

  • Insulation monitoring according to IEC/EN 61557-8
  • 2 separate adjustable response thresholds (using e.g. for pre-Alarm and Alarm)
  • Setting range of 1st response value (Pre-Alarm): 20 kΩ … 1 MΩ:
  • Setting range of 2nd response value (Alarm): 10 kΩ … 250 kΩ
  • 2 changeover contacts für insulation failures-Pre-Alarm and -Alarm
  • Energized or de-energized on trip can be selected for indicator relay
  • LED for status indication
  • Automatic and manual device self-test
  • Alarm storage selectable
  • Protection against manipulation by sealable transparent cover
  • External control input for combined Test-/Reset-button
  • 3 wide voltage input for auxiliary voltage
  • Width 52.5 mm

Insulation monitor RN 5897/320

Advantages

  • Suitable for DC charging stations for electric vehicles acc. to IEC/EN 61851-23:2014/AC:2016-06
  • Insulation monitoring according to IEC/EN 61557-8
  • Connection of an external coupling device RL 5898 for voltages up to AC 400 V / DC 500 V or RP 5898 for voltages up to AC 690 V / DC 1000 V
  • Extended operating temperature range of – 40 … + 70 °C
  • Very fast reaction time ≤ 1 s
  • Optimised insulation resistance monitoring also during mains voltage variation
  • Self-test every full operating hours
  • Preventive fire and system protection
  • Detection of symmetric and asymmetric insulation faults
  • Universal application in non-earthed AC, DC, AC/DC networks
  • Easy adjustment of response values and setting parameter via rotational switch
  • Suitable for large leakage capacitances up to 5 μF
  • Monitoring also with voltage-free mains
  • Measuring circuit L1(+)/L2(-) with broken wire detection (can be switched off)
  • Protective conductor PE1/PE2 with broken wire detection (can’t be switched off)

Features

  • 2 separate adjustable response thresholds (using e.g. for pre-alarm and Alarm)
  • Setting range of 1st response value (Pre-alarm): 20 kΩ … 500 kΩ
  • Setting range of 2nd response value (alarm): 1 kΩ … 100 kΩ
  • 1 changeover contacts each for insulation failures-Pre-alarm and -alarm
  • Energized or de-energized on trip can be selected for indicator relay
  • With multicolour status LED to indicate the state of operation.
  • Automatic and manual device self-test
  • Alarm storage selectable
  • Protection against manipulation by sealable transparent cover
  • External control input for combined test- / reset-button with additional Stop of the measuring function
  • 3 wide voltage input for auxiliary voltage
  • Additional coupling device is necessary
  • Width 52.5 mm

Insulation monitor RN 5897/321

Advantages

  • Suitable for DC charging stations for electric vehicles acc. to IEC/EN 61851-23:2014/AC:2016-06
  • Insulation monitoring according to IEC/EN 61557-8
  • Universal application in non-earthed AC-, DC-, AC/DC networks up to AC max. 250 V resp. DC max. 300 V
  • Connection of an external coupling device RL 5898 for voltages up to AC 400 V / DC 500 V or RP 5898 for voltages up to AC 690 V / DC 1000 V possible
  • Extended operating temperature range of – 40 … + 70 °C
  • Very fast reaction time ≤ 1 s
  • Optimised insulation resistance monitoring also during mains voltage variation
  • Self-test every full operating hours
  • Preventive fire and system protection
  • Detection of symmetric and asymmetric insulation faults
  • Easy adjustment of response values and setting parameter via Modbus
  • Suitable for large leakage capacitances up to 5 μF
  • Monitoring also with voltage-free mains
  • Measuring circuit L(+)/L(-) with broken wire detection (can be switched off)
  • Protective conductor PE1/PE2 with broken wire detection (can’t be switched off)
  • With galvanic separated Modbus RTU interface

Features

  • 2 separate adjustable response thresholds (using e.g. for pre-alarm and Alarm)
  • Setting range of 1st response value (Pre-alarm): 20 kΩ … 500 kΩ
  • Setting range of 2nd response value (alarm): 1 kΩ … 100 kΩ
  • 1 changeover contacts each for insulation failures-Pre-alarm and -alarm
  • Energized or de-energized on trip can be selected for indicator relay
  • With multicolour status LED to indicate the state of operation.
  • Automatic and manual device self-test
  • Alarm storage selectable
  • Protection against manipulation by sealable transparent cover
  • External control input for combined test- / reset-button with additional Stop of the measuring function
  • 2 wide voltage input for auxiliary voltage
  • Width 52.5 mm

Insulation monitor IP 5880

Advantages

  • Preventive fire and system protection
  • For single and 3-phase AC-systems up to 0 … 500 V and 10 … 10000 Hz
  • Monitors also disconnected voltage systems
  • Easy adjustment of response values

Features

  • According to IEC/EN 61557-8
  • Adjustable tripping value RAL of 5 … 100 kΩ or 10 … 500 kΩ
  • De-energized on trip
  • Auxiliary voltage Measuring Circuit and output contacts are galvanically separated
  • Manual and auto reset
  • With test and reset button
  • Connections of external test and reset buttons possible
  • LED indicators for operation and alarm
  • 2 changeover contacts
  • IL/SL 5880/200 with additional prewarning
    – Adjustable prewarning value 10 kΩ … 5 MΩ
    – Output function programmable
  • Variant IL/SL 5880/300 according to DIN VDE 0100-551 for mobile generator sets available
  • 4 models available:
    IL 5880, IP 5880: 61 mm deep with terminals near to the bottom to be mounted in consumer units or industrial distribution systems according to DIN 43880
    SL 5880, SP 5880: 98 mm deep with terminals near to the top to be mounted in cabinets with mounting plate and cable ducts
  • DIN rail or screw mounting
  • 35 mm width

Insulation monitor IP 5880/711

Features

  • According to IEC/EN 61 557-8
  • For rooms used for medical purposes
    according to IEC 60364-7-710, DIN VDE 0100-710
  • For three-phase and A.C. power systems with 0 … 500 V 
    and 10 … 1000 Hz (IT power systems)
  • Adjustable alarm value for ground fault RAL of 50 … 500 kΩ
  • Measuring circuit with broken wire protection
  • As option, programmable for storing or non-storing of errors
  • With reset and test button
  • Additional external reset and test buttons can be connected
  • LED indicators for operation, insulation fault, and interruption of Measuring circuit
  • 2 changeover contacts
  • With LED chain for indication of the current insulation status
  • IP 5880/711 for connection of the test and display panel UP 5862
  • 52.5 mm width
 

Insulation monitor RP 5888

Features

  • Increasing the availability of machines and plants
  • For preventive maintenance
  • According to IEC/EN 61 557-8
  • With configurable analogue output for insulating value
  • For three-phase and A.C. power systems with 0 … 500 V and 10 … 1000 Hz
  • Adjustable alarm value for ground fault RAL of 5 k … 5 MΩ
  • Monitors also disconnected voltage systems
  • Energized / de-energized on trip settable
  • Measuring circuit, auxiliary voltage, output contacts and analogue output are galvanically separated
  • Programmable for manual reset or hysteresis function
  • With test and reset button
  • Connections for external test and reset buttons possible
  • LED indicators for operation and alarm
  • 2 changeover contacts
  • Output function programmable
  • Width: 70 mm

Insulation monitor LK 5894

Advantages

  • Preventive fire and system protection
  • Quick fault localisation through selective earth fault detection to L+ and L-
  • Universal application in non-earthed AC, DC, AC/DC networks with up to 690 V nominal voltage
  • Suitable for large leakage capacitances up to 1000 μF
  • Simplest setting via engaging rotary switches
  • Optimised measuring times – normally shorter than with known methods
  • Monitoring also with voltage-free mains
  • Measuring circuit with broken wire detection
  • No additional coupling device required

Features

  • Insulation monitoring according to IEC/EN 61557-8
  • Detection of symmetric and asymmetric insulation faults
  • 2 changeover contacts
  • Prewarning threshold setting range: 20 kΩ … 2 MΩ
  • Alarm threshold setting range: 1 kΩ … 250 kΩ
  • Energized or de-energized on trip can be selected for output relay
  • Setting the maximum leakage capacitance to shorten the response time
  • Simple, clearly arranged adjustment of the device with screwdriver
  • LED chain to indicate the current insulation resistance
  • Display of active measuring circuits
  • Automatic and manual device self-test
  • Width: 90 mm

Insulation monitor LK 5895

Advantages

  • Preventive fire and system protection
  • Quick fault localisation through selective earth fault detection to L+ and L-
  • Universal application in non-earthed AC, DC, AC/DC networks
    with up to 1000 V nominal voltage
  • Suitable for large leakage capacitances up to 3000 μF
  • Simplest setting via engaging rotary switches
  • For monitoring photovoltaic system, also with thin-film technology
  • Optimised measuring times – normally shorter than with known methods
  • Monitoring also with voltage-free mains
  • Measuring circuit with broken wire detection
  • No additional coupling device required

Features

  • Insulation monitoring according to IEC/EN 61557-8
  • Detection of symmetric and asymmetric insulation faults
  • Measuring circuits can be disconnected via control terminals, e.g. for mains couplings
  • 1 changeover contact each for prewarning and alarm
  • Prewarning threshold setting range: 20 kΩ … 2 MΩ
  • Alarm threshold setting range: 1 kΩ … 250 kΩ
  • Energized or de-energized on trip can be selected for output relay
  • Setting the maximum leakage capacitance to shorten the response time
  • Simple, clearly arranged adjustment of the device with screwdriver
  • LED chain to indicate the current insulation resistance
  • Display of active measuring circuits
  • Automatic and manual device self-test
  • Alarm storage selectable
  • External test and reset pushbutton can be connected
  • Width 90 mm

Insulation monitor LK 5896

Advantages

  • Preventive fire and system protection
  • Quick fault localisation through selective earth fault detection to L+ and L-
  • Universal application in non-earthed AC, DC, AC/DC networks with up to 1000 V nominal voltage
  • Suitable for large leakage capacitances up to 3000 μF
  • Simplest setting via engaging rotary switches
  • For monitoring photovoltaic system, also with thin-film technology
  • Optimised measuring times – normally shorter than with known methods
  • Monitoring also with voltage-free mains
  • Additional measuring circuit allows AC output monitoring even with the inverter switched off, e.g. with hybrid vehicles
  • Measuring circuit with broken wire detection
  • No additional coupling device required
  • Trigger output for insulation fault locating system
  • Analogue output for value of the insulation resistance: 0 … 10 V / 0 … 20 mA (2 … 10 V / 4 … 20 mA)

Features

  • Insulation monitoring according to IEC/EN 61557-8
  • Detection of symmetric and asymmetric insulation faults
  • Measuring circuits can be disconnected via control terminals, e.g. for mains couplings
  • 1 changeover contact each for prewarning and alarm
  • 3. output relay for signalling wire break and device faults
  • Prewarning threshold setting range: 20 kΩ … 2 MΩ
  • Alarm threshold setting range: 1 kΩ … 250 kΩ
  • Energized or de-energized on trip can be selected for output relay
  • Setting the maximum leakage capacitance to shorten the response time
  • Simple, clearly arranged adjustment of the device with screwdriver
  • LED chain to indicate the current insulation resistance
  • Display of active measuring circuits
  • Automatic and manual device self-test
  • Alarm storage selectable
  • External test and reset pushbutton can be connected
  • Width: 90 mm

Insulation monitor LK 5896/900

Advantages

  • Preventive fire and system protection
  • System for sequential monitoring of separated voltage systems, that can be coupled
  • Quick fault localisation through selective earth fault detection to L+ and L-
  • Universal application in non-earthed AC, DC, AC/DC networks with up to 1000 V nominal voltage
  • Suitable for large leakage capacitances up to 3000 μF
  • Simplest setting via engaging rotary switches
  • Optimised measuring times – normally shorter than with known methods
  • Monitoring also with voltage-free mains
  • Measuring circuit with broken wire detection
  • No additional coupling device required
  • Analogue output for value of the insulation resistance: 0 … 10 V / 0 … 20 mA (2 … 10 V / 4 … 20 mA)

Features

  • Insulation monitoring according to IEC/EN 61557-8
  • Detection of symmetric and asymmetric insulation faults
  • 1 changeover contact each for prewarning and alarm
  • 3. output relay for signalling wire break and device faults
  • Prewarning threshold setting range: 20 kΩ … 2 MΩ
  • Alarm threshold setting range: 1 kΩ … 250 kΩ
  • Energized or de-energized on trip can be selected for output relay
  • Setting the maximum leakage capacitance to shorten the response time
  • Simple, clearly arranged adjustment of the device with screwdriver
  • LED chain to indicate the current insulation resistance
  • Display ” measuring circuits active”
  • Display “Master” or “Slave”
  • Automatic and manual device self-test
  • Alarm storage selectable
  • External test and reset pushbutton can be connected
  • With watchdog timer to monitor the trigger signal
  • Width: 90 mm

IT Line monitor IR 9112/710

Features

  • According to IEC/EN 60255-1, IEC/EN 61557-8
  • For rooms used for medical purposes according to IEC 60364-7-710, DIN VDE 0100-710
  • Consisting of:
  • Current monitoring system
    – Measuring ranges of 5 … 50 A (with external converter 50 / 5 A)
    – Adjustable from 0.1 … 1 IN
    – Hysteresis fixed at approx. 4%
    – Adjustable switching delay
    – LED indicators for correct status and overcurrent
    – 2 changeover contacts
  • Temperature monitoring system
    – Detection of temperature overrange
    – Deetection of wire breakage in the sensor circuit
    – Input P1 / P2 for 1 … 6 thermistors
    – LED for auxiliary voltage and contact position
    – 2 changeover contacts
  • Insulation monitoring
    – For straight three-phase and A.C. power systems with 0 … 300 V and 10 … 1000 Hz
    – Fixed alarm threshold for ground fault RAL of 50 kΩ … 500 kΩ
    – With line breakage monitoring function of the Measuring circuit
    – Optionally, programmable for storing or non-storing of errors
    – With reset and test key
    – Additional external reset and test keys can be connected
    – LED indicators for operability, insulation error, and interruption of Measuring circuit
    – 2 changeover contacts
  • With LED chain do display the momentary status of insulation and/or connection of the test and indication panel UP 5862, as option (width 140 mm)
  • 105 mm width

IT Line monitor IS 9112/711

Features

  • According to IEC/EN 60255-1, IEC/EN 61557-8
  • For rooms used for medical purposes according to IEC 60364-7-710, DIN VDE 0100-710
  • Consisting of:
  • Current monitoring system
    – Measuring ranges of 5 … 50 A (with external converter 50 / 5 A)
    – Adjustable from 0.1 … 1 IN
    – Hysteresis fixed at approx. 4%
    – Adjustable switching delay
    – LED indicators for correct status and overcurrent
    – 2 changeover contacts
  • Temperature monitoring system
    – Detection of temperature overrange
    – Deetection of wire breakage in the sensor circuit
    – Input P1 / P2 for 1 … 6 thermistors
    – LED for auxiliary voltage and contact position
    – 2 changeover contacts
  • Insulation monitoring
    – For straight three-phase and A.C. power systems with 0 … 300 V and 10 … 1000 Hz
    – Fixed alarm threshold for ground fault RAL of 50 kΩ … 500 kΩ
    – With line breakage monitoring function of the Measuring circuit
    – Optionally, programmable for storing or non-storing of errors
    – With reset and test key
    – Additional external reset and test keys can be connected
    – LED indicators for operability, insulation error, and interruption of Measuring circuit
    – 2 changeover contacts
  • With LED chain do display the momentary status of insulation and/or connection of the test and indication panel UP 5862, as option (width 140 mm)
  • 105 mm width

IT Line monitor IS 9112/712

Features

  • According to IEC/EN 60255-1, IEC/EN 61557-8
  • For rooms used for medical purposes according to IEC 60364-7-710, DIN VDE 0100-710
  • Consisting of:
  • Current monitoring system
    – Measuring ranges of 5 … 50 A (with external converter 50 / 5 A)
    – Adjustable from 0.1 … 1 IN
    – Hysteresis fixed at approx. 4%
    – Adjustable switching delay
    – LED indicators for correct status and overcurrent
    – 2 changeover contacts
  • Temperature monitoring system
    – Detection of temperature overrange
    – Deetection of wire breakage in the sensor circuit
    – Input P1 / P2 for 1 … 6 thermistors
    – LED for auxiliary voltage and contact position
    – 2 changeover contacts
  • Insulation monitoring
    – For straight three-phase and A.C. power systems with 0 … 300 V and 10 … 1000 Hz
    – Fixed alarm threshold for ground fault RAL of 50 kΩ … 500 kΩ
    – With line breakage monitoring function of the Measuring circuit
    – Optionally, programmable for storing or non-storing of errors
    – With reset and test key
    – Additional external reset and test keys can be connected
    – LED indicators for operability, insulation error, and interruption of Measuring circuit
    – 2 changeover contacts
  • With LED chain do display the momentary status of insulation and/or connection of the test and indication panel UP 5862, as option (width 140 mm)
  • 105 mm width