You are here:

DOLD BA 9053 – Current Relay

Brand
DOLD
Part number
BA 9053
Order number
0053101

Current Relay

  • Preventive maintenance
  • For better productivity
  • Quicker fault locating
  • Precise and reliable
Category: SKU: DOLD-0053101 Tags: Brand:
Download datasheet (PDF)Ask an engineer

Price and lead time on request — add this part to your quote list and we will reply with pricing and availability.

Brand

DOLD

Housing width

45 mm

Output contacts

2 C/O contacts

Enclosure design

Switch cabinet

Phases

1

Order number

0053101

The current relay BA 9053 of the VARIMETER series monitors single phase DC or AC voltage systems (with 1 Measuring range for AC and DC). The adjustment is made via potentiometers on the front of the device. Early recognition and preventive maintenance avoid interruptions of electrical plants and provides a higher operational and plant safety.

Features

  • According to IEC/EN 60255-1, IEC/EN 60947-1
  • To: Monitor DC and AC
  • Measuring ranges from 2 mA to 25 A
  • Optionally with 3 measuring ranges 0.1 up to 25 A
  • High overload possible
  • Input frequency up to 5 kHz
  • Galvanic separation between auxiliary circuit – measuring ciruit
  • Auxiliary supply AC and AC/DC
  • Optionally with start-up delay
  • With time delay, up to max. 100 sec
  • Optionally with safe separation to IEC/EN 61140 (on request)
  • As option with manual reset
  • Option with fixed settings possible
  • LED indicators for operation and contact position
  • Width: 45 mm

Technical specifications

1- / 3-phase 1
Auxiliary voltage AC, AC/DC, DC
Enclosure design Switch cabinet
Measuring range AC, DC 0,002 – 25 A
Operate delay Yes
Output contacts 2 C/O contacts
Width 45 mm
Type BA 9053

Available variants

Auxiliary voltage AC/DC 24 – 80 V · AC/DC 80 – 230 V · AC/DC 80 – 250 V · AC 110 V · AC 230 V · AC 240 V · AC 400 V · DC 12 V
Contact equipping 1 changeover contact · 2 changeover contacts
Measuring range AC 0,1 – 1 A · AC 0, 1 – 1 A · AC 0,5 – 5 A · AC 1 – 10 A · AC 1 A/ 5 A/ 10 A · AC 1,5 – 15 A · AC 1A/ 5A/ 10 A · AC 2 – 20 A · AC 2 – 20 mA · AC 2,5 – 25 A · AC 5 A/10 A/ 25 A · AC 10 – 150 Hz 0,1 – 1 A · AC 10 – 150 Hz 0,5 – 5 A · AC 10 Hz 1 – 10 A · AC 10 Hz 1,5 – 15 A · AC 16 2/3 Hz 0,1 – 1 A · AC 16 2/3 Hz 0,5 – 5 A · AC 16 2/3 Hz 1 – 10 A · AC 16 2/3 Hz 2 – 20 A · AC 20 – 200 Ma · AC 20 mA/ 200 mA/ 1A · AC 30 – 300 mA · AC 50 – 500 mA · AC 80 – 800 mA
Start up delay 1 – 20 s · 1 – 30 s · 1 – 60 s · 1 – 100 s · Without
Switching delay 0 – 1 s · 0 – 20 s · 0 – 30 s · 0 – 60 s · 0 – 100 s
Approvals and Markings UKCA · UKCA, CCC
Variant Overcurrent relay. De-energized on trip. Time delay at response value · Overcurrent relay. De-energized on trip. Time delay at response value. With 3 current ranges. 1 C/O contact · Overcurrent relay. De-energized on trip. Time delay at response value. With manual reset, resetting by disconnecting the power supply · Overcurrent relay. Energized on trip. Time delay at response value · Overcurrent relay. Energized on trip. Time delay at response value. With 3 current ranges. 1 C/O contact · Overcurrent relay. Energized on trip. Time delay at response value. With 5 um gold plated contacts · Overcurrent relay. Energized on trip. Time delay at response value. With manual reset, resetting by disconnecting the power supply · Undercurrent relay. De-energized on trip. Time delay at hysteresis value · Undercurrent relay. De-energized on trip. Time delay at hysteresis value. With 3 current ranges. 1 C/O contact · Undercurrent relay. De-energized on trip. Time delay at hysteresis value. With manual reset, resetting by disconnecting the power supply · Undercurrent relay. Energized on trip. Time delay at hysteresis value · Undercurrent relay. Energized on trip. Time delay at hysteresis value. With 3 current ranges. 1 C/O contact · Undercurrent relay. Energized on trip. Time delay at hysteresis value. With 5 um gold plated contacts · Undercurrent relay. Energized on trip. Time delay at hysteresis value. With manual reset, resetting by disconnecting the power supply

Tell us the variant you need in your quote request.