| Brand | DOLD |
|---|---|
| Housing width | 35 mm |
| Output contacts | 2 C/O contacts |
| Enclosure design | Switch cabinet |
| Phases | 1, 3 |
| Order number | 0051677 |
You are here:
DOLD SL 9171 – Undervoltage Relay
- Brand
- DOLD
- Part number
- SL 9171
- Order number
- 0051677
Undervoltage Relay
Download datasheet (PDF)Ask an engineer
Price and lead time on request — add this part to your quote list and we will reply with pricing and availability.
Monitoring of voltage systems on undervoltage. Automatic switching to emergency supply or of emergency light in the case of phase loss according to DIN VDE 0100-710 or DIN VDE 0108.
Features
- According to IEC/EN 60255-1
- Monitoring of undervoltage in 3-phase system
- Also for single phase
- Without auxiliary supply
- Optionally for 3p3w systems
- LED indicator for state of output relay
- Independent of phase sequence
- 1 or 2 changeover contacts
- Optionally fixed or settable response value
- As option with phase sequence detection
- Optionally with or without N
- Optionally with off-delay t1
- Opionally with on delay t2
- Devices available in 2 enclosure versions:I-model: depth 59 mm, with terminals at the bottom for installation systems and industrial distribution systems according to DIN 43 880S-model: depth 98 mm, with terminals at the top for cabinets with mounting plate and cable duct
- Width:IK 9171, SK 9171: 17.5 mmIL 9171, SL 9171: 35 mm
Technical specifications
| 1- / 3-phase | 1, 3 |
|---|---|
| Auxiliary voltage | Without |
| Enclosure design | Switch cabinet |
| Nominal voltage max. | 3/N AC 500 / 290 V |
| Operate delay | Yes |
| Output contacts | 2 C/O contacts |
| Width | 35 mm |
| Type | SL 9171 |
Available variants
| Contact equipping | 2 changeover contacts |
|---|---|
| Nominal voltage | 3/N AC 110 / 63 V · 3/N AC 220 / 127 V · 3/N AC 400 / 230 V · 3/N AC 480 / 277 V · 3AC 110 V · 3AC 400 V · 3AC 500 V |
| Response value | 0,7 Un · 0,55 – 1,05 Un · 0,85 Un |
| Time delay | 0,5 – 20 s · without |
| Variant | With N. NC circuit operation. Settable time delay t1. Fixed response value · With N. NC circuit operation. Settable time delay t1. Settable response value · With N. NC circuit operation. Settable time delay t2. Fixed response value · With N. NC circuit operation. Settable time delay t2. Settable response value · With N. NC circuit operation. Without time delay. Fixed response value · With N. NC circuit operation. Without time delay. Settable response value · Without N. NC circuit operation. Settable time delay t1. Fixed response value · Without N. NC circuit operation. Settable time delay t1. Settable response value · Without N. NC circuit operation. Settable time delay t2. Fixed response value · Without N. NC circuit operation. Settable time delay t2. Settable response value · Without N. NC circuit operation. Without time delay. Fixed response value · Without N. NC circuit operation. Without time delay. Settable response value |
Tell us the variant you need in your quote request.