| Brand | DOLD |
|---|---|
| Housing width | 35 mm |
| Output contacts | 2 C/O contacts |
| Enclosure design | Switch cabinet |
| Phases | 1, 3 |
| Order number | 0054172 |
DOLD SL 9079 – Short-time Voltage Drop Relay
- Brand
- DOLD
- Part number
- SL 9079
- Order number
- 0054172
Short-time Voltage Drop Relay
- Preventive maintenance
- For better productivity
Price and lead time on request — add this part to your quote list and we will reply with pricing and availability.
The voltage relays IL 9079 and SL 9079 of the VARIMETER series detect short undervoltages or short phase failures. Monitoring is simple and does not require a great deal of wiring, as no auxiliary voltage is required. Early detection of impending failtures and preventive maintenance prevent costly damage and as a user you benefit from the operational safety and high availability of your system.
Features
- According to IEC/EN 60255-1
- Fast detection of undervoltage or phase failure in three-phase voltage systems
- Detects auto reclosing of 20 ms
- Adjustable response value 0.55 … 1.05 UN
- Operate delay to generate a defined reset signal
- Manual reset possible with external circuit
- Single-phase connection possible
- Optionally fixed response value 0.8 UN
- De-energized on trip
- Green LED indicate for closed contact
- Independant of phase sequence
- 3p4w connection
- Optionally for 3p3w systems
- 2 changeover contacts
- Devices available in 2 enclosure versions:IL 9079: Depth 59 mm, with terminals at the bottom for installation systems and industrial distribution systems according to DIN 43880SL 9079: Depth 98 mm, with terminals at the top for cabinets for mounting plate and cable duct
- Width 35 mm
Technical specifications
| 1- / 3-phase | 1, 3 |
|---|---|
| Auxiliary voltage | Without |
| Enclosure design | Switch cabinet |
| Nominal voltage max. | 3 AC 500 V |
| Operate delay | Yes |
| Output contacts | 2 C/O contacts |
| Width | 35 mm |
| Type | SL 9079 |
Available variants
| Contact equipping | 2 changeover contacts |
|---|---|
| Nominal voltage | 3AC 230 / 400 V · 3AC 400 V · 3AC 440 V · 3AC 500 V |
| Response value | 0,7 – 1,05 Un · 0,8 – 1,05 Un · 0,8 Un · 0,55 – 1,05 Un |
| Time delay | 0,2 – 2 s |
| Variant | For 3p3w systems. Adjustable response value · For 3p3w systems. Adjustable response value. With transformator for mains with harmonic content · For 3p3w systems. Fixed response value · For 3p4w systems. Fixed response value · For systems with neutral conductor. Adjustable release value |
Tell us the variant you need in your quote request.







