| Brand | DOLD |
|---|---|
| Housing width | 70 mm |
| Output contacts | 2 C/O contacts |
| Enclosure design | Distribution board |
| Phases | 3 |
| Order number | 0043896 |
DOLD IP 9075 – Fuse Monitor
- Brand
- DOLD
- Part number
- IP 9075
- Order number
- 0043896
Fuse Monitor
- Increased system availability through early detection of fuse failures, which can cause considerable damage to systems
- Rapid detection of fuse failures, even when consumers are switched off, ensures system availability at the earliest possible point in time
- Reliable detection of fuse failure, even with an unbalanced or harmonic network and with regenerative motors
Price and lead time on request — add this part to your quote list and we will reply with pricing and availability.
The fuse monitors IL/IP/SL/SP 9075 of the VARIMETER series monitor up to 3 load fuses. Early detection of blown fuses, even when loads are switched off, and preventive maintenance prevent costly damage and, as a user, you benefit from the operational reliability and high availability of your system.
Features
- According to IEC/EN 60255-1
- Recognizes fuse failures in three-phase mains up to 3 AC 690 V
- Can be used for all types and sizes of fuses
- Independent of phase sequence
- Shorter response time than with motor circuit-breakers
- As option:- Energized on trip (output relay activated in the event of a fault)- De-energized on trip (output relay not activated in the event of a fault) with IP 9075 programmable via X4-X5 or X3-X4
- As option with manual reset function and remote reset, programmable via X1-X2
- 2 LED indicators
- As option: 1 NO contact or 2 changeover contacts
- Devices available in 2 enclosure versions:I-model: Depth 59 mm, with terminals at the bottom for installation systems and industrial distribution systems according to DIN 43880S-model: Depth 98 mm, with terminals at the top for cabinets with mounting plate and cable duct
- IL 9075, SL 9075: Width 35 mmIP 9075, SP 9075: Width 70 mm
Technical specifications
| 1- / 3-phase | 3 |
|---|---|
| Enclosure design | Distribution board |
| Measuring range max. | 690 V |
| Output contacts | 2 C/O contacts |
| Standard measuring range | 3 AC 380 – 415 V |
| Width | 70 mm |
| Type | IP 9075 |
Available variants
| Contact equipping | 2 changeover contacts |
|---|---|
| Nominal voltage | AC 380 – 440 V 50 – 400 Hz · AC 480 – 550 V 50 – 400 Hz · AC 600 – 690 V 50 – 400 Hz |
| Variant | Energized / De-energized on trip programmable. Automatic reset · Energized / De-energized on trip programmable. Manual reset programmable |