Thermistor Motor Protection Relay

  • Reliable temperature monitoring of motors
  • Rapid fault location
Download datasheet (PDF)Ask an engineer

Price and lead time on request — add this part to your quote list and we will reply with pricing and availability.

Brand

DOLD

Housing width

22.5 mm

Output contacts

2 C/O contacts

Enclosure design

Switch cabinet

Order number

0055452

Temperature monitoring of explosion protected Motors by „extended safety“ EX e EN 60079-7, „pressure proof enclosure“ EX d EN 60079-1 or „overpressure enclosure“ Ex px in gas containing atmosphere as well as „protection by enclosures“ Ex t EN 60079-31 in dust containing atmosphere. The thermistor Motor protection relay protects Standard and Explosion proof Motor against overheating due to overload accoding to EN 60079-14 and EN 60079-0.

Features

  • According to EN 60947-5-1, EN 60947-8, EN 60079-14, EN 61508, EN 50495, EN 13849
  • Detection of- Overtemperature- Broken wire in sensor circuit- Short circuit in sensor circuit
  • 1 input for 3 or 6 PTC-reistors
  • Functions as options or settable with DIP-switches:- Automatic reset (fault is not stored)- Manual reset (fault is stored)- Manual reset only on start-up- Manual reset on and also after start-up
  • No voltage safe manual reset
  • Closed circuit operation
  • LED indicators for- Auxiliary supply- Contact position- Overtemperature, broken wire or short-circuit in sensor circuit
  • 2 changeover contacts
  • Button for reset function
  • Remote reset via terminals X1 / X2 (NO contact)
  • Optionally safe separation according to EN 61 140, EN 60 947-1, 6 kV/2 between:- Auxiliary voltage and measuring circuit- Auxiliary voltage and output contacts- Measuring circuit and output contacts- The 2 changeover contacts (only with 2 changeover contacts)
  • Width 22.5 mm

Technical specifications

Auxiliary voltage AC, DC
Classification Thermistor-Motorschutz
Enclosure design Switch cabinet
Measuring range max. > 3.1 kΩ
Output contacts 2 C/O contacts
Width 22,5 mm
Type MK 9003 ATEX

Available variants

Auxiliary voltage AC 24 V · AC 110 V · AC 230 V · AC 400 V · DC 24 V
Contact equipping 2 changeover contacts
Approvals and Markings ATEX
Variant Automatic reset. With short circuit detection. Without safe separation · Automatic reset. With short circuit detection. With safe separation · Function programmable on S1 and S2. With short circuit detection. Without safe separation · Function programmable on S1 and S2. With short circuit detection. With safe separation · Manual reset. With short circuit detection. Without safe separation · Manual reset. With short circuit detection. With safe separation

Tell us the variant you need in your quote request.