| Brand | DOLD |
|---|---|
| Housing width | 52.5 mm |
| Approvals | UL |
| Enclosure design | Distribution board |
| Order number | 0066451 |
DOLD RN 5883 – Residual current monitor, Type B
- Brand
- DOLD
- Part number
- RN 5883
- Order number
- 0066451
Residual current monitor, Type B
- Preventive fire and system protection
- Increasing the availability of plants by early fault detection
- Universal usage at AC/DC mains
- Protection against manipulation by sealable transparent cover over setting switches
Price and lead time on request — add this part to your quote list and we will reply with pricing and availability.
The AC/DC sensitive residual current monitor RN 5883 allows an early detection of insulation faults and detects differential currents with AC as well as DC components in grounded voltage systems (type B). The measurement takes place via an external current transformer.
Contrary to an RCD the residual current monitor RN 5883 does not disconnect the mains when detecting a fault but only indicates it. Besides the easy to read LED chain indicating the actual current several LEDs display operation, pre-alarm and alarm. The 4 measuring ranges cover 10 to 3 A. Additional features are broken wire detection, test function and adjustable pre-alarm.
The residual current monitor RN 5883 provides early information for precise and cost effective maintenance before the plant stops.
Features
- According to IEC/EN 62020, VDE 0663
- For AC and DC systems Type B
- To detect earth faults in grounded voltage systems
- 4 setting ranges from 10 mA to 3 A
- Manual reset, with alarm and pre-warning
- With adjustable switching delay
- Energized or de-energized on trip
- LED indicator for operation, pre-alarm and alarm
- With test function
- LED-chain indicates fault current
- As option with analogue output
- Broken wire detection
- Width: 52.5 mm
Technical specifications
| Adjustable measuring ranges | 0,01 – 3 A |
|---|---|
| Approvals | UL |
| Broken conductor detection | Yes |
| Classification | Type B (AC, DC even and pulsating) |
| Clear key | Yes |
| Enclosure design | Distribution board |
| Operate delay | Yes |
| Relay contact / output | Yes |
| Test key | Yes |
| Type of voltage | AC, DC |
| Width | 52,5 mm |
| Type | RN 5883 |
Available variants
| Auxiliary voltage | AC/DC 24 – 80 V · AC/DC 80 – 230 V · DC 12 – 24 V |
|---|---|
| Contact equipping | 1 changeover contact for prewarning, 1 changeover contact for alarm |
| Measuring range | 10 – 3000 mA |
| Time delay | 0 – 10 s |
| Approvals and Markings | – · CCC · UL-listed C/US, CCC |
| Variant | For current transformer ND5015/024, ND5015/035. With analogue output · For current transformer ND5015/024, ND5015/035. Without analogue output · For current transformer ND5015/024, ND5015/035. Without analogue output. Pre-alarm message and alarm message not storing, reset time 2 s · For current transformer ND5015/070. With analogue output · For current transformer ND5015/070. Without analogue output · For current transformer ND5018/105, ND5018/140, ND5018/210. With analogue output · For current transformer ND5018/105, ND5018/140, ND5018/210. Without analogue output |
Tell us the variant you need in your quote request.