You are here:

DOLD RP 9810 – Voltage and frequency monitor according to VDE-AR-N 4105:2011-08

Brand
DOLD
Part number
RP 9810
Order number
0064814

Voltage and frequency monitor according to VDE-AR-N 4105:2011-08

  • Easy adjustment via rotational switch
  • Precise adjustment and indication of setting values
  • Indication, diagnostics and fault presentation via display
  • Protection against manipulation by sealable transparent cover over setting switches
  • Mains and system protection for your generator set
Category: SKU: DOLD-0064814 Tags: Brand:
Download datasheet (PDF)Ask an engineer

Price and lead time on request — add this part to your quote list and we will reply with pricing and availability.

Brand

DOLD

Housing width

70 mm

Output contacts

3 C/O contacts

Enclosure design

Distribution board

Phases

3

Order number

0064814

The voltage and frequency module RP 9810 monitors in domestic generator sets the mains of the energy supplier. It is built up in a redundant way and each of the 2 channels act on a separate output relay. The adjustment is made via rotational switches. The factory default setting is according to the description in VDE-AR-N 4105:2011-08.

Features

  • According to VDE-AR-N 4105:2011-08
  • Following DIN VDE 0126-1-1:2013-08
  • According to DIN EN 60255-1
  • Can be used according to EEG 2012 and SysStabV
  • Voltage and frequency monitoring for generator sets >30 kVA on public grid, as option also for ≤ 30kVA
  • Fail-safe because of 2-channel structure
  • Certificate of conformity (test certificate) of the BG ETEM
  • Monitoring of the section switches with measuring of response time
  • System test via test button
  • Isolated grid detection
  • Manual reset
  • With additional enabling input, e.g. for ripple control receiver
  • Connection or re-connection after adjustable delay time tw
  • Factory setting according to VDE-AR-N 4105:2011-08
  • Random controlled disconnection in the range of 50.2 Hz and 51.5 Hz for non-regulated power generation systems
  • Protection against manipulation by sealable transparent cover over setting switches
  • Additional fault signalling relay output
  • High measuring accuracy
  • Installion type enclosure 4TE (width x height x depth: 70 x 90 x 71 mm)

Technical specifications

1- / 3-phase 3
Auxiliary voltage Without
Enclosure design Distribution board
Operate delay Yes
Output contacts 3 C/O contacts
Supply voltage 3/N AC 400/230 V
Width 70 mm
Type RP 9810

Available variants

Contact equipping 3 changeover contacts
Generator system power < 30 kVA · > 30 kVA
Supply voltage 3/N AC 400/230 V
Variant – · With additional display of operating data

Tell us the variant you need in your quote request.