| Brand | DOLD |
|---|---|
| Housing width | 105 mm |
| Enclosure design | Distribution board |
| Order number | 0066143 |
DOLD IR 5882 – Residual current monitor, Type A, with integrated transformer
- Brand
- DOLD
- Part number
- IR 5882
- Order number
- 0066143
Residual current monitor, Type A, with integrated transformer
- Preventive fire and system protection
- Increasing the availability of plants by early fault detection
- With internal residual current transformer
- Protection against manipulation by sealable transparent cover over setting switches
Price and lead time on request — add this part to your quote list and we will reply with pricing and availability.
The residual current monitor IR 5882 of the VARIMETER RCM series is used for early detection of insulation faults and detects residual currents with alternating currents and pulsating direct currents in earthed systems (type A). The residual current measurement is carried out via an integrated current transformer. In contrast to the residual current circuit breaker, the residual current monitor IR 5882 does not immediately switch off the mains when a fault is detected, but only indicates the fault. LEDs indicate operational readiness, pre-alarm and alarm. Other features include a check and delete function. The IR 5882 residual current monitor thus offers an information advantage for targeted and cost-effective maintenance measures before the system comes to a standstill.
Features
- According to IEC/EN 62020
- For AC and pulsating DC currants Type A to IEC/TR 60755
- 9 tripping values from 10 mA to 10 A or from 10 mA … 30 A
- Frequency range 20 … 2000 Hz
- Selection of manual or automatic reset
- With prewarning
- With test and reset button
- Short reaction time
- With adjustable delay tv
- De-energized on trip
- LED indication for auxiliary supply and state of contact
- 2 x 1 changeover contact
- 63 mm deep with terminals near to the bottom to be mounted in consumer units or industrial distribution systems according to DIN 43880- Width 105 mm- With internal residual current transformer
Technical specifications
| Adjustable measuring ranges | 0,01 – 10 A |
|---|---|
| Broken conductor detection | Yes |
| Classification | Type A (AC, DC pulsating) |
| Clear key | Yes |
| Enclosure design | Distribution board |
| Operate delay | Yes |
| Relay contact / output | Yes |
| Test key | Yes |
| Type of voltage | AC, DC pulsating |
| Width | 105 mm |
| Type | IR 5882 |
Available variants
| Auxiliary voltage | AC/DC 24 – 230 V |
|---|---|
| Contact equipping | 1 changeover contact for prewarning, 1 changeover contact for alarm |
| Measuring range | 10 A |
| Time delay | 5 s |
| Approvals and Markings | UKCA |
| Variant | Inner diameter current transformer 21.5 mm · Inner diameter current transformer 28 mm |