You are here:

DOLD SL 5881 – Insulation monitor

Brand
DOLD
Part number
SL 5881
Order number
0054627

Insulation monitor

  • Preventive fire and system protection
  • For DC voltage systems up to 12 … 280 V
  • Wide voltage range of measuring input UN DC 12 … 280 V (on request DC 24 … 500 V with separate auxiliary supply, Measuring range 20 … 500 kΩ)
  • Easy adjustment of response value
  • Selective ground fault indication for L+ and L- allows fast fault finding
Category: SKU: DOLD-0054627 Tags: Brand:
Download datasheet (PDF)Ask an engineer

Price and lead time on request — add this part to your quote list and we will reply with pricing and availability.

Brand

DOLD

Housing width

35 mm

Enclosure design

Switch cabinet

Order number

0054627

The insulation monitor IL 5881 of the series VARIMETER IMD monitors the insulation resistance of non-earthed DC systems (IT-systems) with nominal voltage up to DC 12 … 280 V. The supply voltage (auxiliary voltage) is taken from the monitored system. The device has LEDs to indicate the operating status. The response value can be set in a user-friendly way on the front of the device via a potentiometer.

Features

  • With reference to IEC/EN 61557-8 (see also section “Notes”)
  • Adjustable tripping value RAL of 5 … 200 kΩ or 10 … 500 kΩ
  • Selective ground fault indication for L+ and L- allows fast fault finding
  • Without auxiliary supply
  • De-energized on trip
  • 2 changeover contacts
  • Automatic or manual reset, programmable
  • With test and reset buttons
  • Connection for external test and reset button possible
  • Galvanic separated AC or DC auxiliary supply available as option
  • Adjustable time delay as option
  • 2 models available:IL 5881: 61 mm deep with terminals near to the bottom to be mounted in consumer units or industrial distribution systems according to DIN 43880SL 5881: 98 mm deep with terminals near to the top to be mounted in cabinets with mounting plate and cable ducts
  • DIN rail or screw mounting
  • 35 mm width

Technical specifications

Auxiliary voltage AC, DC, Without
Earth fault indicator Yes
Enclosure design Switch cabinet
IMD type DC
Nominal voltage IT system DC 12 – 280 V, DC 24 – 500 V
Response value 5 – 500 kΩ
Response value type Adjustable
Width 35 mm
Type SL 5881

Available variants

Alarm value 5 – 200 kOhm · 20 – 500 kOhm
Auxiliary voltage AC 220 – 240 V · DC 24 V · Without
Contact equipping 2 changeover contacts
Nominal voltage DC 12 – 280 V · DC 24 – 500 V
Time delay 0,5 – 20 s · without
Approvals and Markings UKCA
Variant With auxiliary supply · With auxiliary supply. No alarm at UN < 3 V · Without auxiliary supply. With time delay · Without auxiliary voltage

Tell us the variant you need in your quote request.

Downloads