You are here:

DOLD SL 9079 – Short-time Voltage Drop Relay

Brand
DOLD
Part number
SL 9079
Order number
0054172

Short-time Voltage Drop Relay

  • Preventive maintenance
  • For better productivity
Category: SKU: DOLD-0054172 Tags: Brand:
Download datasheet (PDF)Ask an engineer

Price and lead time on request — add this part to your quote list and we will reply with pricing and availability.

Brand

DOLD

Housing width

35 mm

Output contacts

2 C/O contacts

Enclosure design

Switch cabinet

Phases

1, 3

Order number

0054172

The voltage relays IL 9079 and SL 9079 of the VARIMETER series detect short undervoltages or short phase failures. Monitoring is simple and does not require a great deal of wiring, as no auxiliary voltage is required. Early detection of impending failtures and preventive maintenance prevent costly damage and as a user you benefit from the operational safety and high availability of your system.

Features

  • According to IEC/EN 60255-1
  • Fast detection of undervoltage or phase failure in three-phase voltage systems
  • Detects auto reclosing of 20 ms
  • Adjustable response value 0.55 … 1.05 UN
  • Operate delay to generate a defined reset signal
  • Manual reset possible with external circuit
  • Single-phase connection possible
  • Optionally fixed response value 0.8 UN
  • De-energized on trip
  • Green LED indicate for closed contact
  • Independant of phase sequence
  • 3p4w connection
  • Optionally for 3p3w systems
  • 2 changeover contacts
  • Devices available in 2 enclosure versions:IL 9079: Depth 59 mm, with terminals at the bottom for installation systems and industrial distribution systems according to DIN 43880SL 9079: Depth 98 mm, with terminals at the top for cabinets for mounting plate and cable duct
  • Width 35 mm

Technical specifications

1- / 3-phase 1, 3
Auxiliary voltage Without
Enclosure design Switch cabinet
Nominal voltage max. 3 AC 500 V
Operate delay Yes
Output contacts 2 C/O contacts
Width 35 mm
Type SL 9079

Available variants

Contact equipping 2 changeover contacts
Nominal voltage 3AC 230 / 400 V · 3AC 400 V · 3AC 440 V · 3AC 500 V
Response value 0,7 – 1,05 Un · 0,8 – 1,05 Un · 0,8 Un · 0,55 – 1,05 Un
Time delay 0,2 – 2 s
Variant For 3p3w systems. Adjustable response value · For 3p3w systems. Adjustable response value. With transformator for mains with harmonic content · For 3p3w systems. Fixed response value · For 3p4w systems. Fixed response value · For systems with neutral conductor. Adjustable release value

Tell us the variant you need in your quote request.