| Brand | DOLD |
|---|---|
| Housing width | 52.5 mm |
| Approvals | UL-Recognized |
| Enclosure design | Distribution board |
| Order number | 0069876 |
DOLD RN 5893 – Insulation monitor
- Brand
- DOLD
- Part number
- RN 5893
- Order number
- 0069876
Insulation monitor
- Suitable for DC charging stations for electric vehicles acc. to IEC/EN 61851-23:2014/AC:2016-06
- Preventive fire and system protection
- Detection of symmetric and asymmetric insulation faults
- Quick fault localisation through selective earth fault detection to L+ and L-
- Universal application in non-earthed AC, DC, AC/DC networks up to AC max. 250 V or DC max. 300 V
Price and lead time on request — add this part to your quote list and we will reply with pricing and availability.
The insulation monitor RN 5893 of the VARIMETER IMD family is a solution for optimal insulation monitoring of modern IT systems. The device can be used in the most flexible way for AC, DC and AC/DC systems. Mains areas of applications are non-earthed DC charging stations for electric vehicles with mains voltages up to DC 1000 V. The adjustment of the setting values is simple and user friendly done on 2 rotary switches on the front of the device. Via display and LEDs the measured value, device parameters and device status are indicated easy to read. With a sealable transparent cover the device is protectet against manipulation. The RN 5893 has an additonal Modbus RTU-interface. All measured values, device states and parameters can be read out, set and parameterized. All functions available on the device can also be operated via Modbus.
Features
- Insulation monitoring according to IEC/EN 61557-8
- 2 separate adjustable response thresholds (using e.g. for pre-alarm and alarm)
- Setting value pre-alarm: 1 kΩ … 500 kΩ
- Setting value alarm: 1 kΩ … 500 kΩ
- Energized or de-energized on trip can be selected for indicator relay
- Display for indication of measured value, device parameters and device status
- Manual device self-test (automatic device self-test)
- Alarm storage selectable
- Protection against manipulation by sealable transparent cover
- External control input for combined test- / reset-button with additional Stop of the measuring function
- 2 wide voltage input for auxiliary voltage
- Width 52.5 mm
Technical specifications
| Approvals | UL-Recognized |
|---|---|
| Auxiliary voltage | AC/DC |
| Bus interface | Modbus RTU |
| Classification | For DC charging stations |
| Earth fault indicator | Yes |
| Enclosure design | Distribution board |
| IMD type | AC, AC/DC, DC |
| Nominal voltage IT system | AC 0 – 230 V, AC 0 – 690 (Coupling device) V, DC 0 – 230 V, DC 0 – 1000 (Coupling device) V |
| Response value | 1 – 500 kΩ |
| Response value type | Adjustable |
| Width | 52,5 mm |
| Type | RN 5893 |
Available variants
| Alarm value | 1 – 500 kOhm |
|---|---|
| Auxiliary voltage | AC/DC 24 – 60 V · AC/DC 100 – 240 V |
| Contact equipping | 2 x 1 changeover contact |
| Prewarning value | 1 – 500 kOhm |
| Approvals and Markings | UL-rec. C/US |
| Variant | Für Netzableitkapazitäten bis 5 µF · Für Netzableitkapazitäten bis 30 µF |
Tell us the variant you need in your quote request.