You are here:

DOLD IS 9112/712 – IT Line monitor

Brand
DOLD
Part number
IS 9112/712
Order number
0057877

IT Line monitor

Category: SKU: DOLD-0057877 Tags: Brand:
Download datasheet (PDF)Ask an engineer

Price and lead time on request — add this part to your quote list and we will reply with pricing and availability.

Brand

DOLD

Housing width

140 mm

Enclosure design

Distribution board

Order number

0057877

  • To monitor the IT system of rooms used for medical purposes according to VDE 0100-710
  • Overcurrent and temperature control of the IT isolating transformers
  • Insulation monitoring of the IT power system

Features

  • According to IEC/EN 60255-1, IEC/EN 61557-8
  • For rooms used for medical purposes according to IEC 60364-7-710, DIN VDE 0100-710
  • Consisting of:
  • Current monitoring system- Measuring ranges of 5 … 50 A (with external converter 50 / 5 A)- Adjustable from 0.1 … 1 IN- Hysteresis fixed at approx. 4%- Adjustable switching delay- LED indicators for correct status and overcurrent- 2 changeover contacts
  • Temperature monitoring system- Detection of temperature overrange- Deetection of wire breakage in the sensor circuit- Input P1 / P2 for 1 … 6 thermistors- LED for auxiliary voltage and contact position- 2 changeover contacts
  • Insulation monitoring- For straight three-phase and A.C. power systems with 0 … 300 V and 10 … 1000 Hz- Fixed alarm threshold for ground fault RAL of 50 kΩ … 500 kΩ- With line breakage monitoring function of the Measuring circuit- Optionally, programmable for storing or non-storing of errors- With reset and test key- Additional external reset and test keys can be connected- LED indicators for operability, insulation error, and interruption of Measuring circuit- 2 changeover contacts
  • With LED chain do display the momentary status of insulation and/or connection of the test and indication panel UP 5862, as option (width 140 mm)
  • 105 mm width

Technical specifications

Auxiliary voltage AC
Classification For medically used rooms
Connection for indicator Yes
Earth fault indicator Yes
Enclosure design Distribution board
IMD type AC
Nominal voltage IT system AC 0 – 300 V
Response value 50 – 500 kΩ
Response value type Adjustable
Width 140 mm
Type IS 9112/712

Available variants

Auxiliary voltage AC 230 V
Contact equipping 2 changeover contacts
Variant For rooms used for medical purposes. With 11-stage LED chain for indication of the current insulation value, and connection facility for a test and indicator unit UP 5862

Tell us the variant you need in your quote request.

Downloads