DOLD RN 5897/240 – Insulation monitor

Brand
DOLD
Part number
RN 5897/240
Order number
0069123

Insulation monitor

  • Insulation monitoring according to IEC/EN 61557-8
  • Suitable for DC charging stations for electric vehicles acc. to IEC/EN 61851-23:2014/AC:2016-06
  • Universal application in non-earthed AC, DC, AC/DC networks up to AC max. 250 V or DC max. 300 V
  • With connection facility of an external coupling device RL 5898 for voltages up to AC 400 V / DC 500 V or RP 5898 for voltages up to AC 690 V / DC 1000 V
  • Extended operating temperature range of – 40 … + 70 °C
Category: SKU: DOLD-0069123 Tags: Brand:
Download datasheet (PDF)Ask an engineer

Price and lead time on request — add this part to your quote list and we will reply with pricing and availability.

Brand

DOLD

Housing width

52.5 mm

Approvals

UL

Enclosure design

Distribution board

Order number

0069123

The insulation monitor RN 5897/240 of the VARIMETER IMD family is a solution for optimal insulation monitoring of modern IT systems. The device can be used in the most flexible way for AC, DC and AC/DC systems. The setting of the parameters and the switching values is done by simple and operator friendly rotational switches on front of the device. The operating status is indicated user friendly via a multicolour LED. With a sealable transparent cover the device is protectet against manipulation.

Features

  • Setting range of 2nd response value (alarm): 1 kΩ … 500 kΩ
  • 1 changeover contacts each for insulation failures alarm and device failures
  • Energized or de-energized on trip can be selected for indicator relay
  • With multicolour status LED to indicate the state of operation.
  • Automatic and manual device self-test
  • Alarm storage selectable
  • Protection against manipulation by sealable transparent cover
  • External control input for combined test- / reset-button with additional stop of the measuring function
  • With semiconductor output to indicate the insulation resistance (PWM)
  • 3 wide voltage input for auxiliary voltage
  • Width 52.5 mm

Technical specifications

Approvals UL
Auxiliary voltage AC/DC, DC
Classification For DC charging stations
Earth fault indicator Yes
Enclosure design Distribution board
IMD type AC, AC/DC, DC
Nominal voltage IT system AC 0 – 690 (Coupling device) V, DC 0 – 1000 (Coupling device) V
Response value 1 – 500 kΩ
Response value type Adjustable
Width 52,5 mm
Type RN 5897/240

Available variants

Alarm value 1 – 500 kOhm
Auxiliary voltage AC/DC 24 – 60 V · AC/DC 85 – 230 V · DC 12 – 24 V
Contact equipping 2 x 1 changeover contact
Approvals and Markings UL-listed C/US, CCC

Tell us the variant you need in your quote request.