You are here:

DOLD RN 5897 – Insulation monitor

Brand
DOLD
Part number
RN 5897
Order number
0070034

Insulation monitor

  • Acc. to DIN VDE 0100-551 for mobile generator sets
  • Preventive fire and system protection
  • Detection of symmetric and asymmetric insulation faults
  • Quick fault localisation through selective earth fault detection to L+ and L-
  • Universal application in non-earthed AC, DC, AC/DC networks up to 300 V
Category: SKU: DOLD-0070034 Tags: Brand:
Download datasheet (PDF)Ask an engineer

Price and lead time on request — add this part to your quote list and we will reply with pricing and availability.

Brand

DOLD

Housing width

52.5 mm

Approvals

UL

Enclosure design

Distribution board

Order number

0070034

The insulation monitor RN 5897 of the VARIMETER IMD family is a solution for optimal insulation monitoring of modern IT systems. The device can be used in the most flexible way for AC, DC and AC/DC systems even with large leakage capacity to earth (PE). The adjustment of the setting values is simple and user friendly done on 2 rotary switches on the front of the device. Via display and LEDs the measured value, device parameters and device status are indicated easy to read. With a sealable transparent cover the device is protectet against manipulation.

Features

  • Insulation monitoring according to IEC/EN 61557-8
  • 2 separate adjustable response thresholds (using e.g. for pre-Alarm and Alarm)
  • Setting range of 1st response value (Pre-Alarm): 20 kΩ … 500 kΩ
  • Setting range of 2nd response value (Alarm): 15 kΩ … 100 kΩ
  • 2 changeover contacts für insulation failures-Pre-Alarm and -Alarm
  • Energized or de-energized on trip can be selected for indicator relay
  • Display for indication of measured value, device parameters and device status
  • Setting the maximum leakage capacitance to shorten the response time
  • Automatic and manual device self-test
  • Alarm storage selectable
  • Protection against manipulation by sealable transparent cover
  • External control input for combined Test-/Reset-button
  • 3 wide voltage input for auxiliary voltage
  • Width 52.5 mm

Technical specifications

Approvals UL
Auxiliary voltage AC/DC, DC
Classification For mobile power generators
Earth fault indicator Yes
Enclosure design Distribution board
IMD type AC, AC/DC, DC
Nominal voltage IT system AC 0 – 230 V, DC 0 – 230 V
Response value 1 – 100 kΩ
Response value type Adjustable
Width 52,5 mm
Type RN 5897

Available variants

Alarm value 15 – 100 kOhm
Auxiliary voltage AC/DC 24 – 60 V · AC/DC 85 – 230 V · DC 12 – 24 V
Contact equipping 2 x 1 changeover contact
Prewarning value 20 – 500 kOhm
Approvals and Markings UL-listed C/US, CCC

Tell us the variant you need in your quote request.