You are here:

DOLD IL 9094 – Temperature Monitoring Relay

Brand
DOLD
Part number
IL 9094
Order number
0056024

Temperature Monitoring Relay

  • Preventive maintenance
  • For better productivity
  • Quicker fault locating
Category: SKU: DOLD-0056024 Tags: Brand:
Download datasheet (PDF)Ask an engineer

Price and lead time on request — add this part to your quote list and we will reply with pricing and availability.

Brand

DOLD

Housing width

35 mm

Output contacts

1 C/O contact

Enclosure design

Distribution board

Order number

0056024

The temperature monitoring relays IK 9094, IL 9094, SK 9094, SL 9094 of the VARIMETER series are used for temperature monitoring of motors, ball bearings and rooms. The early detection of impending failures and preventive maintenance prevent costly damage and as a user you benefit from the operational reliability and high availability of your system.

Features

  • According to IEC/EN 60255-1
  • 1 PT100 input, 2-wire connection
  • 3 temperature ranges
  • Adjustable response value
  • Adjustable Hysteresis with wide range 3 … 30 °C or 1 … 15 °C
  • Broken wire detection in sensor circuit
  • Programmable hysteresis or latching function via terminal X1
  • IK 9094 no galvanic separation between measuring and auxiliary circuit
  • Closed circuit operation
  • LED indicator for operation and state of output relay
  • 1 changeover contact
  • As option with response value up to – 50 °C, e.g. for refrigeration plants
  • As option with galvanic separation between measuring and auxiliary circuit
  • Devices available in 2 enclosure versions:I-model: Depth 59 mm, with terminals at the bottom for installation systems and industrial distribution systems according to DIN 43880S-model: Depth 98 mm, with terminals at the top for cabinets with mounting plate and cable duct
  • DIN rail or screw mounting
  • IK 9094, SK 9094: 17.5 mm widthIL 9094, SL 9094: 35 mm width

Technical specifications

Auxiliary voltage AC
Classification Temperaturüberwachung
Enclosure design Distribution board
Measuring range max. 250 °C
Output contacts 1 C/O contact
Width 35 mm
Type IL 9094

Available variants

Auxiliary voltage AC 230 V
Contact equipping 1 changeover contact
Response value -50 – 25 C · 0 – 150 C · 100 – 250 C
Variant With galvanic separation between auxiliary and measuring circuit. Adjustable hysteresis 1 – 15 °C · With galvanic separation between auxiliary and measuring circuit. Adjustable hysteresis 3 – 30 °C