You are here:

DOLD SL 5882 – Residual current monitor, Type A

Brand
DOLD
Part number
SL 5882
Order number
0055515

Residual current monitor, Type A

  • Preventive fire and system protection
  • Increasing the availability of plants by early fault detection
  • With external residual current transformer
  • Protection against manipulation by sealable transparent cover over setting switches
Category: SKU: DOLD-0055515 Tags: Brand:
Download datasheet (PDF)Ask an engineer

Price and lead time on request — add this part to your quote list and we will reply with pricing and availability.

Brand

DOLD

Housing width

35 mm

Enclosure design

Switch cabinet

Order number

0055515

The residual current monitors IL/SL 5882 of the VARIMETER RCM series are suitable for detecting insulation faults in earthed systems as well as for monitoring and preventive maintenance of electrical systems. Insulation deterioration can be detected at an early stage and indicated to the operator of the installation without immediately causing an interruption of operation.

Features

  • According to IEC/EN 62020
  • For AC and pulsating DC currants Type A to IEC/TR 60755
  • 9 tripping values from 10 mA to 10 A or from 10 mA … 30 A
  • Frequency range 20 … 2000 Hz
  • Selection of manual or automatic reset
  • With prewarning
  • With test and reset button
  • Broken wire detection
  • Short reaction time
  • With adjustable delay tv
  • De-energized on trip
  • LED indication for auxiliary supply and state of contact
  • 2 x 1 changeover contact
  • Devices available in 3 enclosure versions:IL 5882: 63 mm deep with terminals near to the bottom to be mounted in consumer units or industrial distribution systems according to DIN 43880- Width 35 mm- For connection of external residual current transformer, e. g. ND 5016, ND 5019 or split current transformer ND 5014SL 5882: 100 mm deep with terminals near to the top to be mounted in cabinets with mounting plate and cable ducts- Width 35 mm- For connection of external residual current transformer, e. g. ND 5016, ND 5019 or split current transformer ND 5014

Technical specifications

Adjustable measuring ranges 0,01 – 10 A, 0,01 – 30 A
Broken conductor detection Yes
Classification Type A (AC, DC pulsating)
Clear key Yes
Enclosure design Switch cabinet
Operate delay Yes
Relay contact / output Yes
Test key Yes
Type of voltage AC, DC pulsating
Width 35 mm
Type SL 5882

Available variants

Auxiliary voltage AC/DC 12 V · AC/DC 24 – 230 V
Contact equipping 1 changeover contact for prewarning, 1 changeover contact for alarm · 2 changeover contact for warning, without prewarning
Measuring range 10 A · 30 A
Time delay 5 s
Approvals and Markings UKCA

Tell us the variant you need in your quote request.

Downloads