| Brand | DOLD |
|---|---|
| Housing width | 35 mm |
| Enclosure design | Distribution board |
| Order number | 0069087 |
DOLD RL 5881 – Insulation monitor
- Brand
- DOLD
- Part number
- RL 5881
- Order number
- 0069087
Insulation monitor
- Preventive fire and system protection
- Detection of symmetric and asymmetric insulation faults
- For non-earthed DC voltage networks up to 300 V
- Suitable for large leakage capacitances up to 30 μF
- Monitoring also with voltage-free mains
Price and lead time on request — add this part to your quote list and we will reply with pricing and availability.
The insulation monitor RL 5881 of the VARIMETER IMD family is a solution for optimal insulation monitoring of modern IT systems. The setting of the parameters and the switching values is done by simple and operator friendly rotational switches on front of the device. The operating status is indicated user friendly via a multicolour LED. With a sealable transparent cover the device is protectet against manipulation.
Features
- Insulation monitoring according to IEC/EN 61557-8
- Adjustable response threshold, Setting range: 1 kΩ … 300 kΩ
- 1 changeover contacts for insulation failure alarm
- De-energized on trip
- Energized on trip on request
- With multicolour status LED to indicate the state of operation
- Automatic and manual device self-test
- Manual reset or hysteresis function selectable (programmable via control input)
- Protection against manipulation by sealable transparent cover
- Control input for external test and reset-button
- 2 wide voltage input for auxiliary voltage
- RL 5881/100 without auxiliary voltage
- Width 35 mm
Technical specifications
| Auxiliary voltage | AC/DC, DC, Without |
|---|---|
| Earth fault indicator | Yes |
| Enclosure design | Distribution board |
| IMD type | DC |
| Nominal voltage IT system | DC 0 – 240 V |
| Response value | 1 – 300 kΩ |
| Response value type | Adjustable |
| Width | 35 mm |
| Type | RL 5881 |
Available variants
| Alarm value | 1 – 300 kOhm |
|---|---|
| Auxiliary voltage | AC/DC 24 – 240 V · DC 12 – 24 V · Without |
| Contact equipping | 1 changeover contact for warning |