You are here:

DOLD RN 5897/010 – Insulation monitor

Brand
DOLD
Part number
RN 5897/010
Order number
0070011

Insulation monitor

  • Preventive fire and system protection
  • Detection of symmetric and asymmetric insulation faults
  • Quick fault localisation through selective earth fault detection to L+ and L-
  • Universal application in non-earthed AC, DC, AC/DC networks up to AC max. 250 V or DC max. 300 V
  • With connection facility of an external coupling device:RL 5898 for voltages up to AC 400 V / DC 500 VRP 5898 for voltages up to AC 690 V / DC 1000 VRR 5898*) for voltages up to AC 1000 V / DC 1500 V
Category: SKU: DOLD-0070011 Tags: Brand:
Download datasheet (PDF)Ask an engineer

Price and lead time on request — add this part to your quote list and we will reply with pricing and availability.

Brand

DOLD

Housing width

52.5 mm

Approvals

DNV, UL

Enclosure design

Distribution board

Order number

0070011

The insulation monitor RN 5897/010 of the VARIMETER IMD family is a solution for optimal insulation monitoring of modern IT systems. The device can be used in the most flexible way for AC, DC and AC/DC systems even with large leakage capacity to earth (PE). The adjustment of the setting values is simple and user friendly done on 2 rotary switches on the front of the device. Via display and LEDs the measured value, device parameters and device status are indicated easy to read. With a sealable transparent cover the device is protectet against manipulation.

Features

  • Insulation monitoring according to IEC/EN 61557-8
  • Trigger output for insulation fault locating system
  • 2 separate adjustable response thresholds (using e.g. for pre-Alarm and Alarm)
  • Setting range of 1st response value (Pre-Alarm): 20 kΩ … 2 MΩ
  • Setting range of 2nd response value (Alarm): 1 kΩ … 250 kΩ
  • 2 changeover contacts für insulation failures-Pre-Alarm and -Alarm
  • Energized or de-energized on trip can be selected for indicator relay
  • Display for indication of measured value, device parameters and device status
  • Setting the maximum leakage capacitance to shorten the response time
  • Automatic and manual device self-test
  • Alarm storage selectable
  • Protection against manipulation by sealable transparent cover
  • External control input for combined Test-/Reset-button
  • 3 wide voltage input for auxiliary voltage
  • Width 52.5 mm

Technical specifications

Approvals DNV, UL
Auxiliary voltage AC/DC, DC
Earth fault indicator Yes
Enclosure design Distribution board
IMD type AC, AC/DC, DC
Nominal voltage IT system AC 0 – 230 V, AC 0 – 1000 (Coupling device) V, DC 0 – 230 V, DC 0 – 1500 (Coupling device) V
Response value 1 – 250 kΩ
Response value type Adjustable
Width 52,5 mm
Type RN 5897/010

Available variants

Alarm value 1 – 250 kOhm
Auxiliary voltage AC/DC 24 – 60 V · AC/DC 85 – 230 V · DC 12 – 24 V
Contact equipping 2 x 1 changeover contact
Prewarning value 20 kOhm – 2 MOhm
Approvals and Markings UL-listed C/US, CCC · UL-listed C/US, CCC, DNV
Variant – · With measuring stop function

Tell us the variant you need in your quote request.

Downloads