| Brand | DOLD |
|---|---|
| Housing width | 35 mm |
| Enclosure design | Distribution board |
| Order number | 0053802 |
DOLD IL 5881 – Insulation monitor
- Brand
- DOLD
- Part number
- IL 5881
- Order number
- 0053802
Insulation monitor
- Preventive fire and system protection
- For DC voltage systems up to 12 … 280 V
- Wide voltage range of measuring input UN DC 12 … 280 V (on request DC 24 … 500 V with separate auxiliary supply, Measuring range 20 … 500 kΩ)
- Easy adjustment of response value
- Selective ground fault indication for L+ and L- allows fast fault finding
Price and lead time on request — add this part to your quote list and we will reply with pricing and availability.
The insulation monitor IL 5881 of the series VARIMETER IMD monitors the insulation resistance of non-earthed DC systems (IT-systems) with nominal voltage up to DC 12 … 280 V. The supply voltage (auxiliary voltage) is taken from the monitored system. The device has LEDs to indicate the operating status. The response value can be set in a user-friendly way on the front of the device via a potentiometer.
Features
- With reference to IEC/EN 61557-8 (see also section “Notes”)
- Adjustable tripping value RAL of 5 … 200 kΩ or 10 … 500 kΩ
- Selective ground fault indication for L+ and L- allows fast fault finding
- Without auxiliary supply
- De-energized on trip
- 2 changeover contacts
- Automatic or manual reset, programmable
- With test and reset buttons
- Connection for external test and reset button possible
- Galvanic separated AC or DC auxiliary supply available as option
- Adjustable time delay as option
- 2 models available:IL 5881: 61 mm deep with terminals near to the bottom to be mounted in consumer units or industrial distribution systems according to DIN 43880SL 5881: 98 mm deep with terminals near to the top to be mounted in cabinets with mounting plate and cable ducts
- DIN rail or screw mounting
- 35 mm width
Technical specifications
| Auxiliary voltage | DC |
|---|---|
| Earth fault indicator | Yes |
| Enclosure design | Distribution board |
| IMD type | DC |
| Nominal voltage IT system | DC 12 – 280 V, DC 24 – 500 V |
| Response value | 5 – 500 kΩ |
| Response value type | Adjustable |
| Width | 35 mm |
| Type | IL 5881 |
Available variants
| Alarm value | 0,2 – 10 kOhm · 1 – 50 kOhm · 5 – 200 kOhm · 10 – 500 kOhm · 20 – 500 kOhm · 25 kOhm – 1 MOhm |
|---|---|
| Auxiliary voltage | AC 220 – 240 V · AC 380 – 415 V · DC 12 V · DC 24 – 60 V · DC 24 V · Without |
| Contact equipping | 2 changeover contacts |
| Nominal voltage | DC 12 – 280 V · DC 24 – 280 V · DC 24 – 500 V · DC 24 V · DC 110 V |
| Time delay | 0,5 – 20 s · without |
| Approvals and Markings | UKCA, CCC |
| Variant | – · No alarm at UN < 3 V · With time delay |
Tell us the variant you need in your quote request.