DOLD RR 5887 – Insulation fault locator

Brand
DOLD
Part number
RR 5887
Order number
0067691

Insulation fault locator

  • Quick correction of insulation faults in complex power networks
  • Universal auxiliary voltage range
  • Easy operation
Category: SKU: DOLD-0067691 Tags: Brand:
Download datasheet (PDF)Ask an engineer

Price and lead time on request — add this part to your quote list and we will reply with pricing and availability.

Brand

DOLD

Housing width

105 mm

Order number

0067691

The locating current injector RR 5886 in connection with the insulation fault locator RR 5887 monitors and localises insulation faults in complex AC/DC networks (IT systems). The external current transformers work independently of each other. They are simply connected to the measuring channels of the insulation fault locator RR 5887 and are calibrated by it. The number of measuring channels is increased by combining several insulation fault locators via a RS-485 bus connection. The search for insulation faults in extensive networks can be refined in this manner. Two different alarm levels facilitate the timely detection of a dangerous insulation state. The devices are operated easily and intuitively thanks to automatic balancing and a clear layout of the setting elements. The early detection and localisation of insulations faults permits their quick and targeted correction. As user you will benefit from the operating reliability and high availability of your system.

Features

  • Insulation troubleshooting in AC, DC and AC/DC networks (IT systems) in connection with the locating current injector RR 5886 according to DIN EN 61557-9 (VDE 0413-9):2009 and DIN EN 61557-1 (VDE 0413-1)
  • Insulation coordination according to IEC 60664-1
  • Connection of max. 4 or 8 current transformers depending on the design
  • RS-485 bus connection to synchronise the test current analysis and optionally for the connection to the Modbus RTU field bus
  • Status output of insulation fault detection via external switching output
  • Memory characteristics adjustable via bridge X1-X2
  • Collective signalling relay to output preliminary warning and alarm states
  • Pushbutton for manual reset of alarm states as well as testing of current transformers and their calibration
  • Terminal connection for the storage of alarm states
  • Width: 105 mm

Technical specifications

Auxiliary voltage AC/DC 24 – 80 V, AC/DC 85 – 230 V
Bus interface Modbus RTU, RS-485
Failure storage Yes
Nominal voltage IT system DC, AC, 3AC 24 – 455 V
Operating mode Slave
Width 105 mm
Type RR 5887

Available variants

Auxiliary voltage AC/DC 24 – 80 V · AC/DC 85 – 230 V
Contact equipping 2 changeover contacts
Variant For industrial plants. 4 measuring channels · For industrial plants. 8 measuring channels · For rooms for medical purposes. 4 measuring channels · For rooms for medical purposes. 8 measuring channels

Tell us the variant you need in your quote request.