You are here:

DOLD RL 9877 – Phase monitor

Brand
DOLD
Part number
RL 9877
Order number
0066426

Phase monitor

  • Preventive maintenance
  • For better productivity
  • Always right directions of motors and pumps
  • Safe monitoring of motors and plants with phase failure detection
  • High repeat accuracy
Category: SKU: DOLD-0066426 Tags: Brand:
Download datasheet (PDF)Ask an engineer

Price and lead time on request — add this part to your quote list and we will reply with pricing and availability.

Brand

DOLD

Housing width

35 mm

Output contacts

1 C/O contact

Approvals

UL

Enclosure design

Distribution board

Phases

1, 3

Order number

0066426

The measuring relays RN 9877 and RL 9877 of the VARIMETER series monitor overvoltage, undervoltage, voltage range, phase asymmetry and phase sequence in 3-phase or single-phase systems. The measurement is very simple and without extensive wiring as there is no auxiliary power supply necessary. The monitoring functions are easily selectable using a single turn switch without complex menu structure. The early detection of up-coming break downs and preventive maintenance avoid expensive damages. As user you profit from the reliability and availability of your plant.

Features

  • According to IEC/EN 60255-1
  • For monitoring of AC 3- and single-phase with 50 /60 Hz
  • Detection of- Overvoltage- Undervoltage- Voltage range excess- Phase failure- Phase asymmetry- Missing neutral e.g. broken neutral wire- And phase sequence in 3-phase systems
  • With or without neutral
  • Without separately auxiliary voltage (internal supply from all 3 phases)
  • Output: 1 changeover contact
  • De-energized on trip
  • Adjustable hysteresis for reset
  • Adjustable switching delay
  • Fast fault detection
  • Width:- RL 9877: 35 mm- RN 9877: 52.5 mm

Technical specifications

1- / 3-phase 1, 3
Approvals UL
Auxiliary voltage Without
Enclosure design Distribution board
Measuring range max. 230 V
Output contacts 1 C/O contact
Standard measuring range 3/N AC 80 – 230 V / 45 – 130 V
Width 35 mm
Type RL 9877

Available variants

Contact equipping 1 changeover contact
Hysteresis – · 4 – 20 %
Measuring voltage 3/N AC 80 – 230 V · 3/N AC 80 – 230 V / 45 – 130 V · 3AC 80 – 230 V
Switching delay 0 – 30 s
Approvals and Markings UL-listed C/US
Variant De-energized on trip. With neutral. Voltage monitoring · De-energized on trip. Without neutral. Voltage monitoring · Detect phase failure. Indications of the missing phase via LED. Can be used with or without neutral

Tell us the variant you need in your quote request.

Downloads