You are here:

DOLD OA 5601 – Safety relays

Brand
DOLD
Part number
OA 5601
Order number
OA5601

Safety relays

Category: SKU: DOLD-OA5601 Tags: Brand:
Download datasheet (PDF)Ask an engineer

Price and lead time on request — add this part to your quote list and we will reply with pricing and availability.

Brand

DOLD

Supply voltage type

DC 6 – 110 V

Approvals

TÜV

Order number

OA5601

  • To be used in circuits for safety applications
  • Escalators and walkways
  • Elevators for men and load
  • Railway technology
  • Medical technology

Features

  • According to DIN EN 61810-1, DIN EN 61810-3 (Type A)
  • With forcibly guided contacts
  • High switching reliability due to crown contacts
  • Clearance and creepage distances:contact – coil ≥ 8 mmcontact – contact ≥ 5.5 mmDouble and reinforced insulation with pollution degree 2Overvoltage category: III
  • High voltage resistance ≥ 4 kV
  • High mechanical service life
  • High temperature rangeat OA 5601 and OA 5602: -40 … +85°Cat OA 5603: -40 … +75°C
  • High continiuous thermal current Ith = 16 A
  • High voltage range 0.7 … 1.6 UN
  • As option wash proof RT III

Technical specifications

Approvals TÜV
Clearance and creepage distances, contact set – coil ≥ 8 mm
Contact equipping 4
Contact material AgNi, AgSnO2
Continuous current 3 x 16 A
Nominal voltage DC 6 – 110 V
Protection type RT II (flux-proof relay), optional RT III (wash-tight)
Relay type OA 5601
Size L x W x H 57 x 20 x 39,5 mm
Temperature range (- / +) -40 – 85 °C
Test voltage (AC) contact set – coil ≥ 4 kV eff
Type acc. to DIN EN 61810-3 A
Type of relay Monostable
Voltage Range UN 0,7 – 1,6