You are here:

DOLD IN 5880/711 – Insulation monitor

Brand
DOLD
Part number
IN 5880/711
Order number
0056884

Insulation monitor

Category: SKU: DOLD-0056884 Tags: Brand:
Download datasheet (PDF)Ask an engineer

Price and lead time on request — add this part to your quote list and we will reply with pricing and availability.

Brand

DOLD

Housing width

52.5 mm

Enclosure design

Distribution board

Order number

0056884

For insulation monitoring of the IT system of rooms used for medical purposes according to VDE 0100-710.

Features

  • According to IEC/EN 61 557-8
  • For rooms used for medical purposesaccording to IEC 60364-7-710, DIN VDE 0100-710
  • For three-phase and A.C. power systems with 0 … 500 V and 10 … 1000 Hz (IT power systems)
  • Adjustable alarm value for ground fault RAL of 50 … 500 kΩ
  • Measuring circuit with broken wire protection
  • As option, programmable for storing or non-storing of errors
  • With reset and test button
  • Additional external reset and test buttons can be connected
  • LED indicators for operation, insulation fault, and interruption of Measuring circuit
  • 2 changeover contacts
  • With LED chain for indication of the current insulation status
  • IP 5880/711 for connection of the test and display panel UP 5862
  • 52.5 mm width

Technical specifications

Auxiliary voltage AC
Classification For medically used rooms
Earth fault indicator Yes
Enclosure design Distribution board
IMD type AC
Nominal voltage IT system AC 0 – 500 V
Response value 50 – 500 kΩ
Response value type Adjustable
Width 52,5 mm
Type IN 5880/711

Available variants

Alarm value 50 – 500 kOhm
Auxiliary voltage AC 220 – 240 V 50 – 400 Hz
Contact equipping 2 changeover contacts
Approvals and Markings UKCA
Variant For rooms used for medical purposes

Tell us the variant you need in your quote request.