| Brand | DOLD |
|---|---|
| Housing width | 22.5 mm |
| Cat. / PL (EN ISO 13849-1) | 4/e |
| SIL (IEC/EN 62061) | 3 |
| Supply voltage type | AC, AC/DC |
| Output contacts | 1 NC contact, 5 NO contacts |
| Approvals | UL |
| Connection | Pluggable cage clamp terminals, Pluggable screw terminals, Screw terminals |
| Order number | 0061923 |
DOLD LG 5929 – Extension module
- Brand
- DOLD
- Part number
- LG 5929
- Order number
- 0061923
Extension module
- Safety contact multiplication
Price and lead time on request — add this part to your quote list and we will reply with pricing and availability.
If more safety cicuits have to be switched, than a safety module provides, the extension module LG 5929 is used. It offers safe and reliable contact multiplication and re-enforcment for safety modules with monitoring of the feedback circuit. Safe semiconductor outputs can be extended by relay output contacts. The extension module has forcibly guided contacts and can be delivered with different contact arrangements.
Features
- Can be used in conjunction with a suitable switchgear / control unit in safety applications as follows:- Up to PL e and category 4 according to EN ISO 13849-1- Up to maximum SIL 3 according to EN IEC 62061- Up to SIL 3 according to EN 61508
- According to EN 50156-1 for furnaces
- Control from semiconductor safety outputs (light curtains, e-stop, etc.) is also possible
- Redundant and forcibly guided contacts
- Output: max. 5 NO contacts or 4 NO contacts / 1 NC contact
- 1-channel or 2-channel connection
- LED indication for operation
- Removeable terminal strips
- Wire connection: also 2 x 1.5 mm2 stranded ferruled, or 2 x 2.5 mm2 solid DIN 46 228-1/-2/-3/-4
- As option with pluggable terminal blocks for easy exchange of devices- With screw terminals- Or with cage clamp terminals
- Width 22.5 mm
Technical specifications
| 1- / 2-channel | 1, 2 |
|---|---|
| Approvals | UL |
| Cat. / PL acc. to EN ISO 13849-1 | 4/e |
| Connection | Pluggable cage clamp terminals, Pluggable screw terminals, Screw terminals |
| Nominal voltage | AC, AC/DC |
| Output contacts max. | 1 NC contact, 5 NO contacts |
| SIL CL acc. to IEC/EN 62061 | 3 |
| SIL acc. to IEC/EN 62061 | 3 |
| Thermal current Ith max. | 5 A |
| Width | 22,5 mm |
| Type | LG 5929 |
Available variants
| Contact equipping | 4 NO contacts, 2 NC contacts for feedback and signal circuit · 5 NO contacts, 1 NC contact for feedback circuit |
|---|---|
| Nominal voltage | AC/DC 24 V · AC/DC 110 – 115 V · AC 110 – 115 V · AC 230 – 240 V |
| Terminal type | fixed terminal blocks with screw terminals · pluggable terminal blocks with cage clamp terminals · pluggable terminal blocks with screw terminals |
| Approvals and Markings | UL-listed C/US, TÜV, CCC |
| Variant | For 1-channel connections · For 2-channel connections |
Tell us the variant you need in your quote request.