| Brand | DOLD |
|---|---|
| Housing width | 52.5 mm |
| Approvals | UL-Recognized |
| Enclosure design | Distribution board |
| Order number | 0069880 |
DOLD RN 5893/100 – Insulation monitor
- Brand
- DOLD
- Part number
- RN 5893/100
- Order number
- 0069880
Insulation monitor
- Suitable for DC charging stations for electric vehicles acc. to IEC/EN 61851-23:2014/AC:2016-06
- Insulation monitoring according to IEC/EN 61557-8
- Universal application in non-earthed AC-, DC-, AC/DC networks up to AC max. 250 V resp. DC max. 300 V
- Connection of an external coupling device RP 5898 for voltages up to AC 690 V / DC 1000 V possible
- Extended operating temperature range of – 40 … + 70 °C
Price and lead time on request — add this part to your quote list and we will reply with pricing and availability.
The insulation monitor RN 5897/100 of the VARIMETER IMD family is a solution for optimal insulation monitoring of modern IT systems. The device can be used in the most flexible way for AC, DC and AC/DC systems. Mains areas of applications are non-earthed DC charging stations for electric vehicles with mains voltages up to DC 1000 V, that need an extended temperature range. The setting of the parameters and the switching values is done via Modbus. All measured values, device statuses and parameters can also be read out via Modbus. All functions of the device can also be operated via Modbus. The operating status is indicated user friendly via a multicolour LED. With a sealable transparent cover the device is protectet against manipulation.
Features
- 2 separate adjustable response thresholds (using e.g. for pre-alarm and Alarm)
- Setting range pre-alarm: 1 kΩ … 500 kΩ
- Setting range alarm: 1 kΩ … 500 kΩ
- 2 parameterizable changeover contacts (for insulation fault pre-alarm, insulation fault-alarm, insulation fault-alarm on DC+/DC- or device fault) each galvanic separated
- Energized or de-energized on trip can be selected for indicator relay
- With multicolour status LED to indicate the state of operation.
- Manual device self-test (automatic device self-test can be activated)
- Alarm storage selectable
- Protection against manipulation by sealable transparent cover
- External control input for combined test- / reset-button with additional Stop of the measuring function
- 2 wide voltage input for auxiliary voltage
- Width 52.5 mm
Technical specifications
| Approvals | UL-Recognized |
|---|---|
| Auxiliary voltage | AC/DC |
| Bus interface | Modbus RTU |
| Classification | For DC charging stations |
| Earth fault indicator | Yes |
| Enclosure design | Distribution board |
| IMD type | AC, AC/DC, DC |
| Nominal voltage IT system | AC 0 – 230 V, AC 0 – 690 (Coupling device) V, DC 0 – 230 V, DC 0 – 1000 (Coupling device) V |
| Response value | 1 – 500 kΩ |
| Response value type | Adjustable |
| Width | 52,5 mm |
| Type | RN 5893/100 |
Available variants
| Alarm value | 1 – 500 kOhm |
|---|---|
| Auxiliary voltage | AC/DC 24 – 60 V · AC/DC 100 – 240 V |
| Contact equipping | 2 x 1 changeover contact |
| Prewarning value | 1 – 500 kOhm |
| Approvals and Markings | UL-rec. C/US |
| Variant | Für Netzableitkapazitäten bis 5 µF |
Tell us the variant you need in your quote request.