The insulation monitor RP 5888 of the VARIMETER IMD family provides best and up to date insulation monitoring of AC-IT systems. The measuring principle is overlay with DC-measuring voltage. The setting of the parameters and the switching values is done by simple and operator friendly rotational switches on front of the device. The operating status is indicated user friendly via three multicolour LEDs. In addition the actual insulation resistance value is available on an analogue output.

Features

  • Increasing the availability of machines and plants
  • For preventive maintenance
  • According to IEC/EN 61557-8
  • With configurable analogue output for insulating value
  • For three-phase and A.C. power systems with 0 … 500 V and 10 … 1000 Hz
  • Adjustable alarm value for ground fault RAL of 5 k … 5 MΩ
  • Monitors also disconnected voltage systems
  • Energized / de-energized on trip settable
  • Measuring circuit, auxiliary voltage, output contacts and analogue output are galvanically separated
  • Programmable for manual reset or hysteresis function
  • With test and reset button
  • Connections for external test and reset buttons possible
  • LED indicators for operation and alarm
  • 2 changeover contacts
  • Output function programmable
  • Width: 70 mm

Technical specifications

Auxiliary voltage AC/DC
Connection for indicator Yes
Earth fault indicator Yes
Enclosure design Distribution board
IMD type AC
Nominal voltage IT system AC 0 – 500 V
Response value 5 – 5000 kΩ
Response value type Adjustable
Width 70 mm
Type RP 5888

Available variants

Alarm value 5 kOhm – 5 MOhm
Auxiliary voltage AC/DC 24 – 80 V · AC/DC 80 – 230 V
Contact equipping 2 x 1 changeover contact
Variant With analogue output