| Brand | DOLD |
|---|---|
| Housing width | 52.5 mm |
| Approvals | UL |
| Enclosure design | Distribution board |
| Order number | 0070034 |
DOLD RN 5897 – Insulation monitor
- Brand
- DOLD
- Part number
- RN 5897
- Order number
- 0070034
Insulation monitor
- Acc. to DIN VDE 0100-551 for mobile generator sets
- Preventive fire and system protection
- Detection of symmetric and asymmetric insulation faults
- Quick fault localisation through selective earth fault detection to L+ and L-
- Universal application in non-earthed AC, DC, AC/DC networks up to 300 V
Price and lead time on request — add this part to your quote list and we will reply with pricing and availability.
The insulation monitor RN 5897 of the VARIMETER IMD family is a solution for optimal insulation monitoring of modern IT systems. The device can be used in the most flexible way for AC, DC and AC/DC systems even with large leakage capacity to earth (PE). The adjustment of the setting values is simple and user friendly done on 2 rotary switches on the front of the device. Via display and LEDs the measured value, device parameters and device status are indicated easy to read. With a sealable transparent cover the device is protectet against manipulation.
Features
- Insulation monitoring according to IEC/EN 61557-8
- 2 separate adjustable response thresholds (using e.g. for pre-Alarm and Alarm)
- Setting range of 1st response value (Pre-Alarm): 20 kΩ … 500 kΩ
- Setting range of 2nd response value (Alarm): 15 kΩ … 100 kΩ
- 2 changeover contacts für insulation failures-Pre-Alarm and -Alarm
- Energized or de-energized on trip can be selected for indicator relay
- Display for indication of measured value, device parameters and device status
- Setting the maximum leakage capacitance to shorten the response time
- Automatic and manual device self-test
- Alarm storage selectable
- Protection against manipulation by sealable transparent cover
- External control input for combined Test-/Reset-button
- 3 wide voltage input for auxiliary voltage
- Width 52.5 mm
Technical specifications
| Approvals | UL |
|---|---|
| Auxiliary voltage | AC/DC, DC |
| Classification | For mobile power generators |
| Earth fault indicator | Yes |
| Enclosure design | Distribution board |
| IMD type | AC, AC/DC, DC |
| Nominal voltage IT system | AC 0 – 230 V, DC 0 – 230 V |
| Response value | 1 – 100 kΩ |
| Response value type | Adjustable |
| Width | 52,5 mm |
| Type | RN 5897 |
Available variants
| Alarm value | 15 – 100 kOhm |
|---|---|
| Auxiliary voltage | AC/DC 24 – 60 V · AC/DC 85 – 230 V · DC 12 – 24 V |
| Contact equipping | 2 x 1 changeover contact |
| Prewarning value | 20 – 500 kOhm |
| Approvals and Markings | UL-listed C/US, CCC |
Tell us the variant you need in your quote request.







